The ADM230KW is our auto manual station process input/output suitable for SIL 1, 2 & 3 applications
Input is any standard configured to accept a 4-20mA signal but and std process current or voltage range may be specified
Output is normally configured for a 4-20mA output but any std current or voltage range may be specified. The sense resistor on the output side of the unit being 50O, developing 0.2-1.0V as either the input or the manual control varies 0-100%.
Typical output range:
Current 4-20mA (into 1200O max), 0-10mA (into 2400O max)
Voltage: 0-5Vdc (min load 250O), 0-10Vdc (min load 500O)
Environmental Condition
Performance
Mounting / Dimensions
Environmental Condition
Storing temperature: -40?C to +70?COperating Ambient: -15?C to +55?CRelative Humidity: 5% to 95% RH (Non-Condensing)
Performance
Accuracy/Linearity: 0.1% Span
Mounting / Dimensions
Enclosure: 50w x 75h x 110d mmMounting: Din rail (TS35) or via corner fixing holes