Sign In
Publication
GRILLES
section 1 SEPT 2005
Part F
R
Aluminium Grilles
supply, exhaust and transfer
ventilation systems
sight / lightproof and fireproof
introduction
ordering details
type border fixing finish
TG2 / 32 / SC / SAA / 300 / 200 / 6
width height quantity
example:
The TG type transfer grille is suitable
for mounting in walls or doors where
transfer ventilation is required
between adjacent areas.
The range features single core
sightproof TG grilles and the double
core lightproof T/TG types.
The various frame configurations
are all available with an optional
removable core. (Not suitable for door mounting). Intumescent core blocks
(type BV60) with a 1 hour fire rating can also be supplied to fit between cores
where the partition depth is suitable.
TG Type grilles can be supplied in sizes ranging from 150mm x 100mm up
to 1200mm x 600mm.
sizes
finish
For all additional available options, border styles, fixings, finishes and
plenums see document PART L
options
type
fixings
TG - T/TG
Standard fixing method is by countersunk screw through the flange - SC
Standard finish is satin anodised aluminium - SAA, except for lightproof types
which are finished with a matt black core.
Transfer air
SIGHT / LIGHT PROOF
2
25 - 57
W & H Opening
5
Dimensions
TG2
H -19
16
TG1
(Door Transfer)
32 25
35 min
Beading
by others
Intumescent
Core
TG
T/TG2 T/TG1 T/TG T/TG2/BV60
57 min
W & H Opening
Dimensions
57 60 min 97 min
40
H +45
SO/TG1
25
TG - T/TG
ARCHED
optional
shapes
POLYGONS OB-OVAL ROUND
Shown are a selection of possible shape options.
DIMENSIONS
Transfer air
R
3
AIR FLOW RATE
NOMINAL
WIDTH (mm)
NOMINAL
HEIGHT (mm)
GRILLE FACE
VELOCITY (m/s)
NR LEVEL
l/s m3/hr
150
50
20
10
5
50
40
30
20
200
300
400
150
500
600
800
1000
100
200
400
300
150
1200
2000
1000
900
800
600
500
400
300
250
200
700
100
6000
5000
4000
3000
2000
1000
900
800
700
600
500
400
50
300
200
500
600
5
4
3
2
1.5
1.0
1500
150
1500
7000
0.75
0.5
2
100
30
STATIC PRESSURE
LOSS (Pa)
FREE AREA m2
0.005
0.02
0.03
0.04
0.06
0.08
0.1
0.2
0.3
0.05
0.01
0.15
SELECTION NOMOGRAM
Transfer air
4
SELECTION EXAMPLE
FREE AREA
STATIC PRESSURE LOSS
35
0.024m2
400 x 200mm GRILLE
PASSING 150l/s NR LEVEL
45Pa
example
Acoustic data is presented in terms of NR levels based on a room absorption factor
of 8dB.
BASIS OF DATA
Transfer air
R
5
introduction
ordering details
type finish
SG / BV60 / SE / 450 / 200 / 6
width height quantity
example:
The fire rated intumescent grille is
designed for use as a fire barrier in
either doors or partitions and has
a 1 hour fire rating in accordance
with BS476 Part 8
“Test methods and criteria for
the fire resistance of elements of
building construction”.
The core of the grille comprises a
lattice of Palusol 210 intumescent
material which swells at air
temperatures above 150°C to
Standard finish for the louvre grilles is stove enamelled white or silver but other
colours and types of paint finish are also available as detailed in PART L.
The SG/BV60 assembly is available in sizes ranging from 150 x 100mm
increasing in 50mm increments to 600 x 600mm.
form an effective smoke and fire seal across the assembly. The cores are
supplied with a set of pressed steel louvre grilles as standard, but can also be
offered with other Brooke Air products such as the TG type transfer grille.
sizes
finish
For all additional available options, border styles, fixings, finishes and
plenums see document PART L
options
type SG - BV60
FIRE RATED GRILLES
FIRE
EXIT
Transfer air
6
W & H Opening
Dimensions
8
Steel Grille (SG)
W / H -2
W / H +50
Intumescent
Core (BV60)
8
6mm Intumescent 40 min
Blade on 20mm pitch
SG - BV60
DIMENSIONS
Transfer air
R
7
AIR FLOW RATE
NOMINAL
WIDTH (mm)
NOMINAL
HEIGHT (mm)
NR LEVEL
l/s m3/hr
50
30
20
10
5
40
30
20
200
For more information on sight / lightproof and fireproof Aluminium Grilles talk to Brooke Air Sales