Sign In
Exclusive only to the BLACKBOX, the G4420 device is able to record & store all electrical waveforms, all the time, with no gaps in the data. It calculates RMS, harmonics, & all desired values from waveforms in post-processing that includes calculations of over 10,000 parameters. Obtain a clear & comprehensive picture of conditions leading up to, during, and after an event. The revolutionary G4420 BLACKBOX is the next generation in power quality analysers and provides accurate detection and isolation of power quality problems for effective preventive maintenance.
Each BLACKBOX measures the following all electrical, power and energy parameters: Voltage & current, per phase, average, unbalance, Frequency, Power & Energy - bi-directional, import, export, net, total, Demand - window, sliding window, Harmonics and Sub-cycle transient event recording.
KEY FEATURES
Sampling Range: Voltage 512 & Current 256 Samples per Cycle.
Voltage Harmonic Measurements: Up to 255TH.
Internal Memory: 4GB.
Ethernet Ports; 2.
Voltage Channels: 3 Phase & Neutral.
Nominal Full Scale: 1000V.
Current Channels: 3 Phase & Neutral.
Blackbox G4420 Warranty: 1 year.
Elspec Blackbox G4400 Series Specifications
Product Series
G4410
G4420
G4430
Voltage Sampling Rate, Maximum Samples/Cycle
256
512
1,024
Voltage Harmonics (Individual, Even, Odd, Total) Up to -
127TH
255th
511th
Type of Analog to Digital Converter
16/201 bit
16/201 bit
16/201 bit
Internal Memory
128 MB
4 GB
16 GB
Transient Detection, Microseconds (50Hz/60Hz)
78.1/65.1µs
39/32.5µs
19.5/16.3µs
Ethernet Ports
1
2
2
Power Over Ethernet (PoE- Out)
-
1
1
Voltage Ride Through on Power Loss (up to)
10 sec.
25 sec.
25 sec.
Applicable Measurement Standards
EN50160, IEEE1159, IEEE519, IEC61000-4-15,IEC61000-4-7, IEC61000-4-30 Class A,IEC62053-22/23 Class 0.2.
Applicable EMC Standards
EN55011 Group 1 Class A, EN61000-6-2, IEC60255EN60439-1 (clauses 7.9.1, 7.9.3, 7.9.4, 7.10.3, 7.10.4),FCC Part 15 Subpart B Class A, IEC61000-3-3.
Voltage Channels
Channels
3 Phase + Neutral.
Nominal Full Scale
1,000 V.
Maximum Peak Measurement
8 kV.
Input Impedance
3 MΩ.
Uncertainty
0.1% of Nominal.
Current Channels
Channels
3 Phase + Neutral.
Nominal Full Scale
5 A.
Maximum Peak Measurement
50 A.
Burden
0.0001 VA @ 5A.
Phase
+0.42° @ 3 A +0.17° @ 5 A.
Uncertainty
0.1% of Nominal.
Frequency Measurement
Fundamental Frequency
42.5 Hz to 69 Hz.
Frequency Resolution
10 mHz.
Frequency Accuracy
+10 mHz.
Physical
Dimensions
175 mm x 232 mm x138 mm.
Weight
1.7 Kg.
Power Supply
Operating Range
100-260 VAC: 50/60 Hz 100-300 VDC.
Auxiliary DC Supply
48 VDC.
Auxiliary Supply - PoE In
PoE In According to 802.3af.
Time Synchronisation
Real Time Clock
20 ppm.
GPS
100-200 µs.
IRIG B
100-200 µs.
SNTP Server
50-100 µs.
DCF-77
+15 ms.
Environmental Conditions
Operation Temperature
-20°C to 70°C (-4°F to 158°F).
Storage Temperature
-40°C to 85°C (-40°F to 185°F).
For more information on Blackbox G4420 Fixed Power Quality Analyser talk to Cuthbertson Laird Group
Enquire Now