Sign In
The revolutionary G4500 BLACKBOX is the next generation in PQ Analysers that provides accurate detection & isolation of PQ problems for effective preventive maintenance. With its’ patented data compression algorithm, the PQZIP, the BLACKBOX stores onboard all the waveforms of every network cycle up to a 1+ year, at a resolution of 1,024 samples per cycle.
The G4500 Portable BLACKBOX continually records & measures over 10,000 electrical parameters automatically, all the time for more than a year. Capture everything & get down to the root cause of all Power Quality issues - Trends, Volts/Amps/Hz, Events, Harmonics, THD, Flicker, Power & Energy.
The wireless G4500 BLACKBOX is equipped with a built-in 802.11 b/g access point and Ethernet router, allowing it for portable analysis from any remote location.
KEY FEATURES
Quick, Easy, Mobile Deployment.
Install Devices on a Temporary Basis as Needed.
Produced Detailed Statistical Records.
Troubleshoot PQ Data at High Resolution.
No. of Inputs: AC - 4 (3 phases & neutral), DC - 1.
Elspec Blackbox 4500 Specifications
Waveform Sampling
Voltage Sampling Rate
1024 Samples/Cycle.
Current Sampling Rate
256 Samples/Cycle.
Voltage Harmonics (Individual, Even, Odd, Total) Up to -
511Th.
Current Harmonics (Individual, Even, Odd, Total) Up to -
127Th.
Type of Analog to Digital Converter
16/201 bit.
Storage Capacity
Internal Memory
32 GB/32TB2.
Power Quality Analysis
transient Detection, Microseconds (50Hz/60Hz)
19.5/16.3µs.
Communication Ports
Ethernet Ports
3.
Wi-Fi Communications (802.11g)
1.
Power Over Ethernet (PoE- Out)
1.
Digital Input
4.
RS-232
1.
RS-485
1.
Physical
Dimensions mm
314 X 84 X 271.
Weight
3.7kg.
Control
Comprehensive web server for local and remote real-time monitoring and control.
Applicable Standards
Measurement Standards
EN50160, IEEE1159, IEEE519, IEC61000-4-15, IEC61000-4-7, IEC61000-4-30 Class A
EMC Standards EN61326, CFR47FCC, CISPR11 Group 1, FCC PART 15 Subpart B,
EN61010-2, IEC61000-3-3, IEC61000-4-2, IEC61000-4-3,
IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-11.
Environmental Standards
IEC60068-2-1, 2, 6, 27, 30, 75.
Safety Standards
EN61010-1:2001 2nd Edition.
Power Supply
Operating Range
100-260 VAC: 50/60 Hz 100-300 VDC.
Auxiliary DC Supply
48 VDC.
Auxiliary Supply
PoE In According to 802.3af.
Battery Backup
2 Hours.
Environmental Conditions
Operation Temperature
0°C - 50°C (32°F - 122 °F).
Storage Temperature
-20°C - 60°C (-4°F - 140 °F).
Time Synchronisation
Real Time Clock
+1 Second per 24 Hours.
GPS
100-200 µs.
IRIG B
100-200 µs.
SNTP Server
50-100 µs.
DCF-77
+15 ms.
Voltage Channels
Voltage Channels
4 (3 Phases + Neut.)+ 1 DC.
Nominal Full Scale
1000 V.
Maximum Peak Measurement
8000 V.
Input Impedance
3 MΩ.
Uncertainty
0.1% of Nominal.
Current Channels
Current Channels
4 (3 Phases + Neut.)+ 1Grn/DC.
Current Channels Receive From Clamp
I1-I4: 0-10 VPk I5: 0-3 VPk.
Uncertainty
0.1% +0.1 mV.
Frequency Measurement
Fundamental Frequency
42.5 Hz to 69 Hz.
Frequency Resolution
10 mHz.
Frequency Accuracy
+10 mHz.
For more information on Blackbox G4500 Portable PQ Analyser talk to Cuthbertson Laird Group