Rugged and waterproof, the CA 6422 earth tester is ideal for intensive use in the field. This tester can be used for 2P and 3P earth measurements. The connections are clearly identified with text markings and colour coding. All the measurements and functions are directly accessible on the instrument's front panel, even when you are wearing gloves.
As soon as it is powered up, the instrument automatically performs a resistance measurement in 2P mode. A short press on the TEST button starts measurements in one-shot 3P mode. A long press on TEST can be used to activate the permanent 3P mode. Internal filtering automatically stabilises the measurement. As soon as it has stabilised, the result is frozen on the display.
A LED indicates the presence of a hazardous voltage which prohibits measurement. If the NOISE symbol flashes, it means that a noise voltage is present. In the event of a noise-filled environment, automatic switching from a frequency of 128 Hz to 256 Hz helps to improve measurement accuracy.
FEATURES
2P resistance/3P earth resistance measurement up to 50 kΩ for highly resistive terrain.
Automatic stabilisation of the measurementy.
Leakage current measurement from 0.5 mA.
Battery recharging via the mains, USB socket or vehicle cigarette lighter.
Connections with text and coloured markings to avoid any risk of errors.
Detection if a hazardous voltage is present, thus prohibiting measurement.
Rugged, waterproof casing for intensive, all-terrain use.
Compliant with IEC 61557-1 and IEC 61557-4.
CA 6422 & CA 6424 Comparison Chart
Instrument Functions
C.A 6422
C.A 6424
Earth resistance measurement (with three rods)
Voltage measurement
Resistance measurement
Mean of the earth measurements at 52, 62 and 72%
Detection of RH too high
Detection of RE too high
Detection of a spurious voltage on USE
Measurement of AC current with an ammeter clamp (optional)
Chauvin Arnoux CA6424 Specifications
Voltage
Range
Resolution
Accuracy
2P Resistance
Range
0.05 - 99.99 Ω / 80.0 - 999.9 Ω / 0.800 - 9.999 kΩ / 8.00 - 50.00 kΩ.
Resolution
0.01 Ω / 1 Ω / 10 Ω / 100 Ω.
Accuracy
+ (2%R + 10 cts) / + (2%R + 2 cts) / +(2%R + 1 ct) / + (2%R + 1 ct).
Cable compensation
3P Earth Resistance
Range
0.5 Ω - 2.000 kΩ.
Resolution
0.01 Ω / 0.1 Ω / 1 Ω.
Accuracy
+(1%R + 10 cts) / +(1%R +2 cts) / +(1%R + 1 ct).
Measurement frequency
128 Hz or 256 Hz.
No-load voltage
+10 V peak.
Measurement mode
One-shot or permanent.
Data storage
Calculation of average
General Specifications
Display
Backlit custom 206-segment LCD.
Measurement mode
R 2P (Ω), R 3P (Ω).
Power supply
6 x LR 6 or AA batteries.
Charger
Automatic power-off
Battery life
> 2,000 x 3P earth measurements at 100 Ω.
Dimensions
223 x 126 x 70 mm.
Weight
1 kg.
Environment
Operation: -10 to +50°C / Storage: -40 to +70°C (without batteries/accumulators).
Protection
Up to 600 V on any of the input terminals.
IP/IK index
IP 65 as per IEC 60529 / IK 04 as per IEC 50102.
Drop test
1 metre as per IEC 61010-1.
Standards / electrical safety
EMC: IEC 61326-1; IEC 61010-2-030 / 600 V CAT IV.
Compliance with IEC 61557
IEC 61557-1 and IEC 61557-5.
Chauvin Arnoux C.A 6422 warranty
24-months.
For more information on Chauvin Arnoux CA6422 Earth Tester talk to Cuthbertson Laird Group