Sign In
The Chauvin F607 harmonics clamp can be clamped around a conductor with just one hand. With a measurement range up to 3000A, its ability to measure AC or DC currents and the exceptional jaw opening capacity, this clamp is ideal for use on switchboards in small or large industrial installations.
Equipped with a fast 12-bit TRMS digital acquisition system, F407 clamps offer particularly accurate measurements. Due to their large bandwidth and high crest factor, these clamps guarantee accurate measurements whatever the type of signal.
IEC 61010 1,000 V CAT IV
The CE standard imposes product design constraints for test and measurement instruments. Professional electrical environments are divided into 4 categories. Category IV offers users the greatest safety. A Category IV instrument can be used on all parts of low-voltage installations. The F607 clamps comply with all the specifications imposed by the standards to guarantee the best possible safety for users.
Harmonics
By monitoring voltage and current harmonics, it is usually possible to determine which loads are polluting the electrical network. With the F407 clamp, the harmonics mode enables you to: determine the harmonic currents produced by non-linear loads, analyse the problems caused by these harmonics, depending on their order (heating of neutral, motors, etc.). THD measurement (THD-f and THD-r) can be used to quantify the harmonics present on the network.
Recording to detect even intermittent faults
This is an important advantage for technicians in the field. In the event of random faults, they no longer have to wait for them to occur: the paperless recorder function enables them to record the relevant parameters over time at a rate which they can define. The instrument automatically stores the average, minimum and maximum values in all the modes (voltage, current, power, etc.). All the parameters will be stored in the instrument’s memory. The programmable acquisition rate allows users to define the recording duration possible on the instrument. All the recordings will then be available as trend curves for analysis.
FEATURES
Up to 2,000A ac or 3,000Adc / ac+dc.
Clamping diam. 60mm.
W, var and VA power measurements.
Harmonics up to the 25th order, THD-f & THD-r.
Harmonic and frequency analysis.
TrueInrush current measurement.
Data recording and Bluetooth communication.
10,000-count triple display.
Chauvin Arnoux F607 Specifications
Clamping Diameter
60 mm.
Display
Backlit LCD.
Resolution
10,000 counts.
Number of Values Displayed
3.
Type of Acquisition
TRMS (AC, AC+DC]/DC).
Autorange
Yes.
Automatic AC / DC detection
Yes.
AC Current
AC Current Range
0.25 to 2,000 A (3,000 A peak).
DC Current Range
0.25 to 1500 A.
A AC+DC
0.25 to 3000 A
(3,000 A peak).
Best Accuracy
1% reading + 3 cts.
AC/DC Voltage
Range
0.15 to 1,000 V.
Frequency
Range
Current: 5.0 to 1000 Hz
Voltage: 5.0 to 20.00 kHz.
Resistance
Range
0.1 to 99.99 kΩ.
Open Circuit Voltage
?8 V.
Measurement Current
?680 µA.
Audible Continuity
Continuity Threshold
40 Ω.
Diode Test
No.
Single-phase and total three-phase power values
Active power
1 W to 2,000 kW.
Reactive power
1 var to 2,000 kvar.
Apparent power
1 VA to 2,000 kVA.
FP / DPF
Yes/Yes.
Harmonic analysis
Yes.
THDf / THDr
Yes / Yes.
Frequency analysis
25th order.
Phase rotation (2-wire method)
-
General
Dimensions
111 x 296 x 41 mm.
Weight
640 g.
Chauvin F407 warranty
3 years.