Sign In
Please Note:
This Chauvin Arnoux PEL104 power logger is NOT supplied with clamps.
The Chauvin Arnoux PEL104 power logger measures and records all the useful data for energy consumption diagnostics. The PEL104 can be used without cutting off the mains power supply.
Portable, rugged and compact, its magnetised casing makes it easy to set up, including in an electrical cabinet. The PEL104 is a logger equipped with 3 voltage channels and 3 current channels. No more battery problems, as the logger self-powers directly via the phase by means of the accessory included.
The backlit LCD screen equipped with a triple digital display is particularly easy to read. The PEL 104 is also equipped with an SD card capable of storing several years' data, an ideal function for measurement campaigns.
FEATURES
Compact magnetised casing.
Communication via Wifi, 3G-UMTS/GPRS, LAN (Ethernet), Bluetooth and USB.
ANDROID application.
Self-powered via its voltage inputs up to 600 V.
Continuous recording with an interval of 200 ms between measurements.
Measurements as per the IEEE 1459 standard.
Measurements of the fundamental active power.
4 voltage inputs and 3 current inputs.
5 measurements per second, simultaneously on each phase.
Active, apparent and reactive power values.
Phase: cos phi, tan PHI, PF.
Harmonics/THD.
Sending of periodic reports by email.
Chauvin Arnoux PEL Product Video
Chauvin Arnoux PEL104 Specifications
Model 103
Display
With quadruple digital display.
Installation types
Single-phase, split-phase, three-phase with or without neutral and many other specific configurations.
Number of channels
4 voltage inputs, 4 current inputs.
Measurements
Network frequency
50 Hz, 60 Hz & 400 Hz.
Voltage (measurement ranges)
10.00 - 1,000 Vac/dc.
Current (depending on sensor)
(measurement ranges)
5 mA ac to 10 kA ac / 50 mA dc to 1.4 kA dc
Calculated Measurements
Ratio
Up to 650,000 V / up to 25,000 A.
Power
10 W to 10 GW / 10 var to 10 Gvar / 10 VA to 10 GVA.
Energy
Up to 4EWh / 4 EVAh / 4 Evarh.
Phase
cos ?, tan ?, PF.
Harmonics
THD.
Complementary Functions
Phase order
Yes.
Min/max
Yes.
Mounting
Hook (optional).
Recording
Sampling / Acquisition rate / Aggregation
5 measurements/s - from 1 min to 60 min.
Memory
SD card 2 GB (SD-HC up to 32 GB).
Communication
Ethernet , Bluetooth, USB, Wifi and GPRS.
Power supply
Power supply via the phase
1,000 V AC/DC.
Safety
IEC 61010 1000 V CAT IV.
Casing
IP67.
Mechanical
Dimensions
245 x 270 180 mm without sensor.
Weight
<3400 g.
Chauvin PEL103 warranty
2 years.
For more information on Chauvin PEL104 Power & Energy Logger talk to Cuthbertson Laird Group
Enquire Now