Sign In
Please Note:
The Chauvin Arnoux PEL106 power logger is NOT supplied with clamps.
The Chauvin PEL106 power logger measures and records all the useful data for energy consumption diagnostics. The PEL106 can be used without cutting off the mains power supply.
Suitable for all types of electrical networks, the PEL106 automatically recognises the sensors connected. It measures voltage up 1,000 VAC/VDC and current up to 10 kVAC / 5 kVDC. Its wide measurement ranges enable it to record power values up to 10 GW/Gvar/GVA, and energy up to 4 EWh/EVAh/Evarh.
Rugged thanks to its IP67 all-terrain casing, the PEL106 can be transported anywhere. It is equipped with 4 voltage channels and 4 current channels. No more battery problems: this logger is self-powered directly via the phase. The LCD screen with backlighting and a quadruple digital display is particularly easy to read. The PEL 106 is equipped with an SD/SD-HC card for backup of the data from several months or even years.
The PEL106 also offers Wifi communication and 3G/GPRS. The 3G/GPRS mode allows users to insert a SIM card in the PEL for remote connection via a GPRS-3G link. It is also possible to access a PEL104 or PEL106 via an IRD server. In this way, when an alarm is triggered, the user can automatically receive an email for real-time notifications.
The PEL106 can be configured as a Wifi access point operating on the 2.4 GHz radio frequency band, allowing you to monitor the measurements in real time with a PC, smartphone, tablet etc. The PEL Transfer software can be used to analyse the data recorded with the PEL100 models. On the basis of the power measurement campaigns performed, the software automatically provides a breakdown of the losses detected.
FEATURES
IP67 all-terrain casing resistant to shock, UV light and high temperatures.
Communication via Wifi, 3G-UMTS/GPRS, LAN (Ethernet), Bluetooth and USB.
Self-powered via its voltage inputs up to 1,000 V.
Continuous recording with an interval of 200 ms between measurements.
Measurements as per the IEEE 1459 standard.
4 voltage inputs & 4 current inputs.
Ideal for installation on electricity poles.
Chauvin Arnoux PEL Product Video
Chauvin Arnoux PEL106 Specifications
Display
With quadruple digital display.
Installation types
Single-phase, split-phase, three-phase with or without neutral and many other specific configurations.
Number of channels
4 voltage inputs, 4 current inputs.
Measurements
Network frequency
50 Hz, 60 Hz & 400 Hz.
Voltage (measurement ranges)
10.00 - 1,000 Vac/dc.
Current (depending on sensor)
(measurement ranges)
5 mA ac to 10 kA ac / 50 mA dc to 1.4 kA dc
Calculated Measurements
Ratio
Up to 650,000 V / up to 25,000 A.
Power
10 W to 10 GW / 10 var to 10 Gvar / 10 VA to 10 GVA.
Energy
Up to 4EWh / 4 EVAh / 4 Evarh.
Phase
cos ?, tan ?, PF.
Harmonics
THD.
Complementary Functions
Phase order
Yes.
Min/max
Yes.
Mounting
Hook (optional).
Recording
Sampling / Acquisition rate / Aggregation
5 measurements/s - from 1 min to 60 min.
Memory
SD card 2 GB (SD-HC up to 32 GB).
Communication
Ethernet , Bluetooth, USB, Wifi and GPRS.
Power supply
Power supply via the phase
1,000 V AC/DC.
Safety
IEC 61010 1000 V CAT IV.
Casing
IP67.
Mechanical
Dimensions
245 x 270 180 mm without sensor.
Weight
<3400 g.
Chauvin PEL103 warranty
2 years.
For more information on Chauvin PEL106 Power Energy Logger talk to Cuthbertson Laird Group
Enquire Now