The Fluke 6200-2 PAT tester is a low weight, small size, one-touch solution with redesigned auto-test capabilities to help you increase the number of portable appliance tests completed each day. The 6200-2 is designed to enable you to work faster without compromising safety - yours or your customer’s.
This PAT tester has Fluke’s traditional ruggedness to be able to withstand working in the field. Packed with all the features you need for testing portable appliances, a Fluke PAT tester is a complete all-in-one solution.
The 6200-2 can perform all the tests required for Class I and Class II appliances and conforms to safety standard EN61010. All features for manual tests and low volume applications are accessible from the front panel.
FEATURES
Dedicated key for each test for ‘one-touch’ testing.
Pre-set pass/fail levels to save time.
Large backlit display for easy reading.
Single mains socket for appliance connection.
Separate IEC socket for easy mains/extension lead testing.
Detachable test leads for quick field replacement.
Integral carrying handle.
USB port for data transfer.
Fluke 6200-2 Specifications
Power-on Test
The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
Display Range
90 V to 264 V.
Accuracy at 50 Hz
+ (2% + 3 counts).
Resolution
1 V.
Input Impedance
> 1 MΩ // 2.2 nF.
Maximum Input Mains Voltage
264 V.
Earth Bond Test (Rpe)
Display Range
0 to 19.99 Ω .
Accuracy (After Bond Test Zeroing)
+ (2.5% + 4 counts).
Resolution
0.01 Ω.
Test Current
200 mA AC -0% +40% into 1.99 Ω
25 A AC + 20% into 25 mΩ at 230 V.
Open Circuit Voltage
> 4 V AC, < 24 V AC.
Bond Test Zeroing
can subtract up to 1.99 Ω .
Insulation Test (Riso)
Display Range
0 to 299 MΩ.
Accuracy
+ (5% + 2 counts) from 0.1 to 300 MΩ.
Resolution
0.01 MΩ (0 to 19.99 MΩ)
0.1 MΩ (20 to 199.9 MΩ)
1 MΩ (200 to 299 MΩ).
Test Voltage
500 V DC -0% + 10% at 500 kΩ load.
Test Current
> 1 mA at 500 kΩ load, < 15 mA at 0 Ω.
Auto Discharge Time
< 0.5 s for 1 µF.
Max. Capacitive Load
Operational up to 1 µF.
Touch Current Test
Display Range
0 to 1.99 mA AC.
Accuracy
+ (4% + 2 counts).
Resolution
0.01 mA.
Internal Resistance (via Probe)
2 kΩ.
Measuring Method
Probe*.
Substitute Leakage Current Test
Display Range
0 to 19.99 mA AC.
Accuracy
+ (2.5% + 3 counts).
Resolution
0.01 mA.
Test Voltage
100 V AC + 20%.
Load/Leakage Test: Load Current
Display Range
0 A to 13 A.
Accuracy
+ (4% + 2 counts).
Resolution
0.1 A*.
Load/Leakage Test: Load Power
Display Range 230 V Mains
0.0 VA to 3.2 kVA.
Accuracy
+ (5 % + 3 counts).
Resolution
1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*.
Load/Leakage Test: Leakage Current
Display Range
0 to 19.99 mA.
Accuracy
+ (4% + 4 counts).
Resolution
0.01 mA*.
*The appliance under test is energised at mains potential.
General Specifications
Operating Temperature
0 to 40 °C.
Power Supply
230 V +10 % -15 %, 50 Hz +2.
Sealing
IP-40 (enclosure), IP-20 (connectors).
Dimensions
200 mm (L) x 275 mm (W) x 114 mm (H).
Weight
3.13 kg.
Fluke 6200-2 warranty
2 years.
For more information on Fluke 6200-2 Portable Appliance Tester talk to Cuthbertson Laird Group