Sign In
The Fluke 985 Particle Counter is the preferred choice for HVAC and IAQ professionals. From filter testing to IAQ investigations, the Fluke 985 is the portable solution for determining airborne particle concentrations. Use the Fluke 985 to immediately respond to occupant complaints, or as part of a comprehensive preventive maintenance program.
With a large screen, intuitive icons for navigation and on-screen data presentation, the Fluke 985 allows users to run more tests quickly, with less time spent cycling through screens to obtain the data. The Fluke 985 is lightweight and easy to use in any position and with easy data export options using USB cable, memory stick it’s easy to review and analyze the data anywhere and anytime.
The Fluke 985 provides particulate data over six channels on a single display, allowing the technician to view all readings at a glance. With the Fluke 985, the technician can configure the number of channels displayed for different particle sizes and also sets an alarm alert via audio or highlighted text for count overconcentration for the particular particle size in concern.
APPLICATIONS:
Measure filter efficiency.
Monitor industrial cleanrooms.
Pre-screen indoor air quality and confidently work with IAQ specialists.
Locate particle sources for remediation.
Report the effectiveness of repairs to customers.
Drive additional business by demonstrating the need for maintenance and repair.
FEATURES:
Six channels and particle size range of 0.3 - 10.0 µm.
Ultra-lightweight and ergonomic design: Promises easy single-hand operation in tight or awkward spaces.
Long battery life: Ten hours of standard-use battery life to last a full work day.
Large 3.5 QVGC Color display: Easy navigation and viewing with the intuitive icons and large font options.
10,000 record storage: Quick access to historical data.
On-screen data presentation: Data can be viewed in a traditional tabular or trend graph view at the user’s preference.
Personalised setting and configurations for the display, sample methods, and alarm settings for sample count.
Data export options: Download data to a PC using a USB memory stick, USB cable or Ethernet connection.
Option password control: Confirms security when required.
USB/Ethernet charge cradle: Assures device is always ready to go when needed.
Fluke 985 Specifications
Measured Specifications
Particle size rate
0.3 µm, 0.5 µm, 1.0 µm, 2.0 µm, 5.0 µm, 10.0 µm.
Channels
6.
Flow Rate
0.1 cfm (2.83L/min).
Light Source
775nm to 795nm, 90mW class 3B laser.
Count Modes
Raw counts, #/m?, #/ft?, #litre in cumulative or differential mode.
Counting Efficiency
50% @ 0.3 µm; 100% for particles > 0.45 µm (per ISO 21501).
Zero Count
1 count/5 minute (JIS B9921).
Concentration Limits
10% at 4,000,000 particles per ft? (per ISO 21501).
Data Storage
10000 records (rotating buffer).
Alarms
User selected particle channels and limits.
Display
QVGA colour with backlight.
Delay Time
0 to 24 hours.
Sample Inlet
Isokinetic probe.
Security
Administrator password controlled (optional).
Communication Mode
USB or Ethernet.
Power Adapter
100 V AC to 240 V AC, 12 V DC, 2.5 A.
Rechargeable Battery
Li-ion 7.4 V 2600 mAh.
Battery Duration/Charge Time
10 hours typical use (5 hours continuous sampling)/3.5 hours.
Operating Environment
50 to 104°F (10 to 40°C)/<95% non-consending relative humidity.
Storage Environment
14 to 122°F (-10 to 50°C)/Up to 98% non-condensing relative humidity.
Dimensions (L x W x D)
27.2 x 9.9 x 5.3 cm (10.7 x 3.9 x 2.1").
Weight
0.68 kg (1.5lbs).
Calibration
PSL particles in air (NIST traceable).
Fluke 985 warranty
1 year.
For more information on Fluke 985 Particle Counter talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.