Sign In
The Fluke BT520 Battery Analyser is a multifunctional meter designed for the test and measurement of a stationary battery system. The BT520 can measure the battery internal resistance and voltages. These measurements can be used to determine the overall condition of the system. It can also measure electrical parameters for battery system maintenance, including dc voltage up to 600 V, ac voltage up to 600 V rms, and ripple voltage.
When testing, the BT520 makes configuring testing procedures significantly easier by guiding the user through how to configure the test. It also includes around 999 record internal memory and is fully downloadable to PC for further interaction with testing data using Fluke's included software package.
FEATURES
Key measurements: Battery resistance, dc and ac voltage, dc and ac current, ripple voltage, frequency and battery temperature.
Sequence measurement mode: Automatic or manual sequence testing of battery strings.
Comprehensive logging: All measured values are automatically captured during testing.
Optimised user interface.
Threshold comparison: Configure multiple reference values and thresholds for resistance and voltage.
Ergonomic test leads.
Enhanced data analysis.
Easy reporting: Generate PDF report on the PC software with analysis graphics.
Wireless communication.
Fluke BT500 Series Quick Demo Video
Fluke BT520 Specifications
Functions
Range
Resolution
Accuracy
BT510
BT520
BT521
Battery Resistance / Strap Resistance1
3 mΩ
0.001 mΩ
1% + 8
30 mΩ
0.01 mΩ
0.8% + 6
300 mΩ
0.1 mΩ
0.8% + 6
3000 mΩ
1 mΩ
0.8% + 6
Vdc
6 V
0.001 V
0.09% + 5
60 V
0.01 V
0.09% + 5
600 V
0.1 V
0.09% + 5
1000 V
1V
0.09% + 5
Vac (45 Hz to 500 Hz with 800 Hz filter)
600 V
0.1 V
2% + 10
Frequency (displayed with Vac and Aac)2
500 Hz
0.1 Hz
0.5% + 8
AC voltage ripple (20KHz Max)
600 mV
0.1 mV
3% + 20
6000 mV
1 mV
3% + 10
Adc/Aac (with accessory Fluke i410)
400 A
1 A
3.5% + 2
Temperature
0°C to 60°C
1°C
2°C (4 °F)
Meter mode
999 records for each measurement position with time stamp.
Sequence mode
Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp.
1 The measurement is based on ac injection method. The injected source signal is < 100 mA, 1 kHz.
2 Trigger level VAC: 10 mV, Aac: 10 A.
Measurement Modes
BT510
BT520
BT521
Resistance (mΩ)
Battery voltage
Voltage dc
Voltage ac and frequency (Hz)
Ripple volt
Temperature of negative battery post
DC and ac current (and frequency)
DMM mode
Sequence mode
Discharge measurement mode
Automatic measurement save
Wireless communication
Memory view
General Specifications
Operating temperature
0°C to 40°C.
Storage temperature
-20°C to 50°C.
Lithium-ion battery charging temperature
0°C to 40°C.
Operating humidity
Non-condensing (10°C).
<=80% RH (at 10°C to 30°C).
<=75% RH (at 30°C to 40°C).
Operating altitude
Sea level to 2000 meters.
Storage altitude
Sea level to 12,000 meters.
IP rating
IP40.
Radio
FCC Class A.
Vibration requirements
MIL-PRF-28800F: Class 2.
Drop test requirements
1 meter.
Temperature coefficients
Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C.
Safety compliance
600 V CAT III.
EMC
IEC 61326.
ROHS
China, Europe.
Protection class 2
Pollution Degree II.
Battery compliance
UN38.3.
UL2054.
IEC62133.
2G per IEC68-2-26, 25G, and 29.
Dimensions (H x W x D)
22 cm x 10.3 cm x 5.8 cm (9 in x 4 in x 2 in).
Weight
850 g (1.9 lb).
Screen dimensions
7.7 cm x 5.6 cm (3 in x 2.2 in).
Interface
USB mini.
Fluke BT520 Warranty
3 years.
For more information on Fluke BT520 Battery Analyser talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.