Sign In
The Fluke PRV240FS Proving Unit is a portable, pocket-sized, battery-powered voltage source. It is specifically built to prove the functionality of the FieldSense measurement on the T6 electrical testers. It also provides ac and dc voltages for other HiZ instruments in your tool box.
The Fluke PRV240FS provides a safe method to verify that your T6 electrical tester is operating properly before you conduct any live tests. The concept of “Test Before Touch” (TBT) involves testing your T6 against a known live source before and after the actual measurement. This sequence verifies that your test tool is operating properly during the actual measurement.
Verify your test tool without unnecessary exposure to shock and arc flash. Using the PRV240FS reduces the need for personal protective equipment (PPE) when a known voltage source is not available for verification of your tester or multimeter before test before TBT are performed. PPE is still needed for absence of voltage testing when appropriate.
Fluke FieldSense technology is a proprietary method of measuring the actual voltage value without making electrical contact. Unlike other non-contact voltage testers and detectors, Fluke’s electrical testers use FieldSense technology to provide an actual voltage measurement. Users get measurements that are more reliable and more accurate than existing go/no-go testers.
FEATURES
Reduces the risk of shock and arc flash by validating the functionality of test tools.
Can prove functionality of the FieldSense measurement on the T6 electrical testers.
Sources both ac and dc steady-state voltage-supplies 240 V dc/ac.
A single switch and a set of LEDs indicate functionality of both the FieldSense “no-test-lead” voltage measurement capability, plus standard ac and dc measurements with test leads.
Compatible with high impedance multimeters or clamp meters.
Voltage is sourced through a central hub designed to test the T6 FieldSense open fork, as well as through recessed contacts that are activated when test probes are inserted to avoid accidental contact.
Includes TPAK magnetic hanging strap.
Long battery life-2000 tests per set of four AA batteries (10 second test average).
Fluke PRV240 FS Specifications
Measurement Specifications
Output voltage
240 V ac rms or dc.
LED power indicators
Turns on when output voltage is present.
Battery
4 x AA Alkaline batteries NEDA 15 A IEC LR6.
Battery life
2000 (10-second duration) test cycles with >1 MΩ load.
Operating temperature
-10 °C to +50 °C.
Safety
I EC61010 -1, I EC61010 -2- 030.
Dimensions (L x W x H)
11.7 cm x 7.4 cm x 4.5 cm (4.6 in x 2.9 in x 1.75 in).
Weight
0. 32 kg (12 oz) includes batteries.
Fluke PRV240FC warranty:
One year.
Electromagnetic Compatibility (EMC)
IEC 61326-1: Controlled Electromagnetic Environment CISPR 11: Group 1, Class A
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object.
For more information on Fluke PRV240FS Proving Unit talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.