Sign In
When you only want to do ‘dead testing’ of appliances that have a physical or rocker on/off switch or no switch at all, the EZYPAT is for you. IT Safe with low current earth bond and 250V insulation test option.
The Tester performs test and indicates PASS/FAIL result complying with the criteria of judgement defined in The IEE Code of Practice for In-service Inspection and Testing of Electrical Equipment: 2003.
FEATURES
Battery operated.
Automatic test sequences.
PASS / FAIL - Green / Red screens.
Appliance status pre-check.
Quick check Continuity.
5 second continuity.
250V Insulation.
500V Insulation.
Substitute leakage test.
Extension Lead Test.
Test lead nulling.
Backlight.
KEWPAT APP
The EZYPAT is a manual tester. The KEWPAT APP is designed to work with it enabling fast documentation. This facilitates record documentation, appliance risk assessment and in conjunction with your SimplyPats Manual+ software, covers your obligations for holding a product register to control your PAT testing.
Fast entry of the essential product information; what, where & ID number. Dropdown menus for:
Customer.
Site.
Location.
Description.
Auto-number increment.
New description or repeat.
Appliance description.
Scan feature for barcodes and QR code.
Kewtech EZYPAT Out Of The Box
Kewtech EZYPAT Specifications
Protective Conductor Resistance Test
Measuring range
0.00 - 20.00 Ω (NULL value inc)*.
Over-range indication
> 20.00 Ω.
Resolution
0.01Ω.
Open-circuit voltage
5 V +0.4 V DC.
Measuring current
200 mA DC (nominal value).
Accuracy
+3% rdg +5 dgt.
* Resistances exceeding 3 Ω cannot be cancelled by NULL function.
Insulation
Rated voltage
250 / 500 V.
Measuring range
0.00 - 20.00 MΩ.
Over-range indication
> 20.00 MΩ.
Resolution
0.01 MΩ.
No-load voltage
250 V DC +20%, -0%
500 V DC +20%, -0%.
Short-circuit current
1.5 mA DC or less.
Rated current
1 -1.2 mA with a load of 0.25 MΩ
1 to 1.2 mA with a load of 0.5 MΩ.
Accuracy
+2% rdg +3 dgt.
Substitute Leakage
Measuring range
0.10 - 12.00 mA rms.
Over-range indication
> 12.00 mA.
Resolution
0.01mA.
Open-circuit voltage/Frequency
30 V +5 V rms / 50 Hz +5%.
Measuring current
1.2 mA AC +0.5 mA (when measuring 12.00 mA).
Accuracy
+3% rdg +5 dgt.
Insulation Test Between L-N
Open-circuit voltage
4.5 V +0.5 V DC.
Criteria of judgement
100 kΩ +20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted.
General
Power
Six size AA alkaline batteries (LR6).
Operating temperature
0°C to +40°C.
Boxed Weight
-20°C to +60°C.
Safety
IEC/EN61010-1 CAT II 300V-instrument
IEC/EN61010-2-030
IEC/EN61010-031 CAT III 600V.
EMC
EN61326-1, 2-2.
Boxed Dimensions
261(L) x 140(W) x 130(D)mm.
Boxed Weight
1.61kg
Kewtech EZYPAT warranty:
2 year warranty subject to product registration.
For more information on Kewtech EZYPAT PAT Tester talk to Cuthbertson Laird Group
Enquire Now