The Kewtech KT66DL 12-in-1 Multifunction Tester has been engineered with pioneering sophisticated loop testing systems, including 3 & 2 wire low current test options and a comprehensive RCD testing facility complete with EV charging point test capacity.
The KT66DL has an easy-to-use single rotary dial with four function softkeys and a colour LCD 3.5” dot matrix display. It also incorporates Anti-Trip Technology (ATT) which electronically bypasses RCDs when performing loop impedance tests. This saves time and money by not having to take the RCD out of the circuit during testing and is a safer procedure to follow.
With the ATT function enabled, a test of 15mA or less is applied between line & earth. It enables loop impedance measurements without tripping RCDs rated at 30mA and above. ATT supports measurements using three wires: Line, Earth, and Neutral and also two wires: Line and Earth.
FEATURES
Simultaneous display of L-N, L-N, L-E voltage (TRMS).
Three modes of starting a test: single press of the test button, continuous testing and by test button in the test probe.
Help display.
Advanced memory - assigns DB, circuit no. and type of test i.e. Zs or Ze.
Two continuity tests 200mA & 15mA .
55V loop test capability - suitable for 110V CTE systems.
Padded neck strap.
Supplied with G7 test leads and additional probe incorporating a test button.
Tests Type AC, ACS, A, AS, F, B, BS & EV.
UC - contact voltage test.
Touch voltage pad with selectable limits.
Heavy duty canvas carry case with extra room for you testing accessories.
The KT66DL has a lid to further protect your instrument. It easily folds under the instrument when in use.
Kewtech KT66DL 12 In 1 Multifunction Tester Specifications
Continuity
Range
20.00/200.0/2000Ω (auto-ranging).
Display range
0.00 - 20.99Ω / 16.0 - 209.9Ω / 160 - 2099Ω.
Measuring range
0 - 2000Ω.
Accuracy
+2.0%rdg+8dgt.
Open-circuit voltage
7 - 14V DC.
Test current
200mA test: 200mA or more (2Ω or less)
15mA test: 15mA+3mA (short-circuit).
Enabled if pre-set NULL value is 9Ω or less. Buzzer: Buzzer sounds when measured resistance is 2Ω or less.
Volts
Range
300.0/600V (Auto-ranging)
Display range
Voltage: 2.0 - 314.9V, 240 - 629V
Frequency: 40.0 - 70.0Hz (displayed at 2V or higher).
Measuring range
Voltage: 2 - 600V
Accuracy
Voltage: +2%rdg+4dgt
Frequency: +0.5%rdg+2dgt.
Uc (RCD)
Mains voltage range
100-260V.
Range
100V.
Display range
0.0 - 104.9V.
Measuring range
0 - 100V.
Accuracy
+5%to+15%rdg +8dgt 230V.
Test current
50 % or less of I?n.
Earth
Precise measurement.
Simplified measurement.
Range
20.00 / 200.0 / 2000Ω (auto-ranging).
Accuracy
20Ω range; +2%rdg+0.08Ω
The other ranges: +2%rdg+3dgt
(Aux. earth resistance: 100Ω).
+2%rdg+0.08Ω
The other ranges: +2%rdg+3dgt.
Output current
20Ω range: approx. 3mA, 200v range: approx. 1.7mA
2000Ω range: approx. 0.7mA Frequency: 825Hz.
Phase Rotation
Measuring Range
48 - 600V / 45 - 65Hz.
Criteria of judgement
Correct sequence: Clockwise symbol and “1, 2, 3” are displayed
Reversed sequence: Counter-clockwise symbol and “3, 2, 1” are displayed.
Insulation
Rated voltage
100V
250V
500V
1000V
SPD (Varistor) 1000V
Range
2.000/20.00/200.0MΩ
auto-ranging
20.00/200.0/1000MΩ
auto-ranging
20.00/200.0/2000MΩ
0 -1000V (increases in 1V steps)
Display range
0.000 - 2.099MΩ
0.00 - 20.99MΩ
0.00 - 20.99MΩ
1049V
1.60 - 20.99MΩ
16.0 - 209.9MΩ
16.0 - 209.9MΩ
16.0 - 209.9MΩ
160 - 1049MΩ
160 - 2099MΩ
Measuring range
0 - 200MΩ
0 - 1000MΩ
0 - 2000MΩ
0 - 1049V
Accuracy
2.000MΩ range: +2%rdg+6dgt
20.00MΩ range: +(2%rdg+6dgt), 200.0MΩ range: +(2%rdg+6dgt)
+5%rdg+5dgt
20.00MΩ range: +2%rdg+6dgt
1000MΩ range: +(5%rdg+6dgt)
2000MΩ range: +(5%rdg+6dgt)
200MΩ range: +5%rdg+6dgt
Rated measurement current
1.0 - 1.2mA
at 100kΩ
1.0 - 1.2mA
at 250kΩ
1.0 - 1.2mA
at 500kΩ
1.0 - 1.2mA
at 1MΩ
1.0 mA
Loop
Function
LOOP ATT
LOOP HIGH
3-Wire L-PE
2-Wire L-PE
L-PE0.01ΩRes
L-PE0.001ΩRes
L-N/L-L
Mains input voltage range
100 - 260V 50/60Hz
(L-N < 20Ω)
48 - 260V 50/60Hz
100 - 260V 50/60Hz
48 - 260V 50/60Hz
Range
LOOP
20.00/200.0/2000Ω (auto-ranging)
20.00/200.0/2000Ω
2.000Ω
20.00Ω
PFC/PSC
2000A/20kA
2000A/20kA (PFC only)
2000A/50kA (PFC only)
2000A/20kA (PSC only)
2000A/20kA (PSC only)
Display range
LOOP
0.00 - 20.99Ω
21.0 - 209.9Ω
210 - 2099Ω
0.00 -20.99Ω
21.0 -209.9Ω
210 -2099Ω
0.00 - 20.99Ω
21.0 - 209.9Ω
210 -2099Ω
0.000 - 2.099Ω
0.00-20.99Ω
PFC/PSC
0 - 2099A
2.10 - 20.99kA
0 - 2099A
2.10 - 20.99kA
(PFC only)
0 - 2099A
2.10 - 50.49kA
(PFC only)
0 - 2099A
2.10 - 20.99kA
(PFC only)
0 - 2099A
2.10 - 20.99kA
(PSC only)
Meas. range
LOOP
0 - 2000Ω
0 - 2000Ω
0 - 2000Ω
0 - 2Ω
0 - 20Ω
Accuracy
LOOP
+(3%rdg+6dgt)
+(3%rdg+10dgt)
+(3%rdg+4dgt)
+(3%rdg+25mΩ)
+(3%rdg+4dgt)
PFC/PSC
Depending on the accuracies of voltage and LOOP measurements.
Test current @ 230V
L-N:6A/60ms
N-PE:10mA (5.3Hz)
L-PE: 15mA
20Ω: 6A/20ms,
200Ω: 0.5A/20ms
2000Ω: 15mA/500ms
25A/20ms
6A/20ms
RCD
Mains input voltage range: 100V - 260V 50/ 60Hz. For Type AC and A RCDs rated at 100mA or higher: 190 - 260V.
Mode
Rated residual operating current (mA)(I?n)
Test current
Duration
Current (mA) rms
Accuracy @230V
Meas. time
Accuracy
x 1/2
AC
G: 10/30/100/300/500/1000 S: 100/300/500
I?nx1/2
-8% to-2% VAR:-10% to 0%
2000ms
Trip Time
+(1%+2ms)
Measuring
time
+3% of FS
A/F
G: 10/30/100/300/500 AS:100/300/500
I?nx1/2
-10% to 0%
B
G: 10/30/100/300 S:100/300
I?nx1/2
-10% to 0%
x 1
AC
G:10/30/100/300/500/1000 S: 100/300/500
I?n
+2% to +8% VAR:0% to +10%
G:550ms
S:1000ms
A/F
G: 10/30/100/300/500 AS:100/300/500
I?nx1.4 (10mA: I?nx2)
0% to +10%
B
G: 10/30/100/300 S:100/300
I?nx2
0% to +10%
6 mA DC
I?n
0% to +10%
10.5s
x 5
AC
G: 10/30/100 S: 100
I?nx5
+2% to +8% VAR:0% to +10%
410ms
A/F
G: 10/30/100 AS: 100
I?nx5x1.4
0% to +10%
B
10/30
I?nx2x5
0% to +10%
Ramp
20 to 110%
AC
10/30/100/300/500 S: 100/300/500
I?n
-4% to +4%
by 10%
G: 300ms
S: 500ms
Measuring
time
+3% of FS
A/F
G: 10/30/100/300/500 AS:100/300/500
I?nx1.4 (10mA:I?nx2)
-10% to +10%
B
G: 10/30/100/300 S: 100/300
I?nx2
-10% to +10%
by 2% /150ms
Ramp EV 30 to 100%
6 mA DC
I?n
-10% to +10%
by 2% / 500ms
-
General
Applicable Standards
IEC 61010-1 CATIII (600V) CATIV (300V) pollution degree 2, IEC 61010 -Tester , -2-030, -2-034,
IEC61557-1,2,3,4,5,6,7,10, IEC 60529 IP40, EN 61326-2-2 (EMC).
Battery type
Size AA Alkaline battery (LR6) x 8.
Display
>Colour Dot Matrix LCD 320(W) X 240(H) pixels.
Operating temperature
-10 to +50°C.
Dimensions
136 (L) x 235 (W) x 114 (D) mm.
Weight
1300g including batteries (8 x AA / LR6).