The Martindale ET4000 Installation Tester carries out all the tests needed to verify the safety of electrical installations in domestic, commercial and industrial wiring installations in accordance with the very latest amendment 3 to the BS7671 17th Edition Wiring Regulations which is effective from January 2015. The ET4000 simplifies 17th edition testing by having the latest amendment 3 fuse tables for Zs values built-in together with red and green LED indicators for instant pass/fail results.
Fast, reliable high current and non-trip loop testing comes as standard together with a high level of input protection and a CAT IV safety rating. The ET4000 includes phase sequence indication and TRMS voltage measurement to cover every job and ensure voltage levels are really within the new Cmin limits defined in amendment 3.
FEATURES
Red and green LED indicators for instant pass/fail results.
Built-in Zs loop impedance tables and help screens.
Automatic polarity and wiring check on connection.
Test and Go soft carry case, no need to unpack and repack.
Auto RCD and ramp test with all results on one screen.
TRMS voltage measurements and phase rotation on all models.
Fast, reliable high current and non-trip loop testing.
Low discharge rechargeable batteries and mains charger.
Martindale ET4000 & ET4500 Multifunction 18th Edition Installation Testers
Martindale ET4000 Specifications
Function
Measuring Range
Resolution
Accuracy
Continuity Resistance
Test current 200 mA 2-wire
0.00 Ω - 19.99 Ω
20.0 Ω - 199.9 Ω
200.0 Ω - 1999 Ω
0.01 Ω
+(3% of rdg + 3 digits)
+(5% of rdg)
+(5% of rdg).
0.1 Ω
1 Ω
Insulation Resistance
Test voltage
50/100/250 V
0.00 MΩ - 19.99 MΩ
20.0 MΩ - 99.9 MΩ
100.0 MΩ - 199.9 MΩ
0.01 MΩ
0.1 MΩ
+(5% of rdg + 3 digits)
+(10% of rdg)
+(20% of rdg).
Test voltage 500/1000 V
0.00 MΩ - 19.99 MΩ
20.0 MΩ - 199.9 MΩ
200 MΩ - 999 MΩ
0.01 MΩ
0.1 MΩ
1 MΩ
+(5% of rdg + 3 digits)
+(5% of rdg)
+(10% of rdg).
RCD Testing
RCD Uc
0.00 V - 19.9 V
20.0 V - 99.9 V
0.1 V
(-0%/+15%) of rdg + 10 digits
(-0%/+15% of rdg).
RCD t
0.00 ms - 40.0 ms
0.0 ms - max.time
0.1 ms
+1 ms
+3 ms.
RCD I ramp
0.2xI?N - 1.1xI?N (AC type)
0.2xI?N - 1.5xI?N (A type, I?N ?30 mA)
0.2xI?N - 2.2xI?N (A type, I?N <30 mA)
0.05xI?N
+0.1xI?N.
Line/Loop Impedance
Zline L-L, L-N Ipsc
L-L, L-N Ipsc
0.00 Ω - 9.99 Ω
10.0 Ω - 99.9 Ω
100 Ω - 999 Ω
1.00 kΩ - 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
+(5% of rdg + 5 digits)
+(10% of rdg).
Zloop L-PE, Ipfc
0.00 Ω - 9.99 Ω
10.0 Ω - 99.9 Ω
100 Ω - 999 Ω
1.00 kΩ - 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
+(5% of rdg+ 5 digits)
+(10% of rdg).
Voltage
TRMS
0 - 550 V
1 V
+(2% of rdg + 2 digits).
Frequency
0.00 Hz - 9.99 Hz
10.0 Hz - 499.9 Hz
0.01 Hz
0.1 Hz
+(0.2% of rdg + 1 digits).
Earth Resistance (ET4500 Only)
3 wire
0.00 Ω - 19.99 Ω
20.0 Ω - 199.9 Ω
200.0 Ω - 9999 Ω
0.01 Ω
0.1 Ω
1 Ω
+(5% of rdg + 5 digits).
General Data
Power Supply
9 VDC (6 x 1.5 V alkaline or rechargeable, size AA).
Measurement Category
CAT III 600 V
CAT IV 300 V.
Protection Classification
Double insulation.
COM Ports
RS232 USB.
Dimensions (L x H x W)
230 x 103 x 115 mm.
Weight
Approx 1.3 kg.