Sign In
The Martindale RC2000 Digital RCD Tester is ideally suited for the testing of Residual Current Protection Devices, in compliance with the 17th Edition of the IEE Wiring Regulations.
The tester is designed to test the most common RCDs in use,with a selector switch providing Fast, I and ½ Trip current settings. The Fast setting provides 150mA trip current for RCDs not exceeding 30mA. The I setting provides full rated trip current, which should cause the RCD under test to trip. The ½ setting provides half the rated trip current whereby the RCD should not trip.
Other features of the RC2000 include a polarity switch with 0° and 180°settings which permits a test cycle to commence with a positive or negative going wave form from the zero cross-over point. The facility to establish whether the system under test is correctly wired is provided by means of neon lamps and monitoring of the voltage present on the earth terminal.
FEATURES:
RCD ratings: 6 mA, 10mA, 30mA, 100mA, 300mA & 500mA.
Half trip: 3mA, 5mA, 15mA, 50mA, 150mA & 250mA.
Test polarity: 0° and 180°.
Timing range: 0 - 1999 mSec.
Thermal and fuse protection.
Supercedes the Metrohm 16R240A.
Martindale RC2000 Specifications
Supply Voltage
240V AC, 50/60 Hz.
RCD Rating (l?n)
6 mA, 10 mA, 30 mA, 100 mA, 300 mA, 500 mA.
Half-Trip Settings (1/2 x l?n)
3 mA, 5 mA, 15 ma, 50 mA, 150 mA, 250 mA.
Fast Trip Settings
150 mA (for l?n=6, 10 and 30 mA only).
Test Polarity
0 and 180°.
Timing Range
0 to 1999 mSec (resolution 1mSec)
Accuracy +2% of reading, +1 digit.
Dimensions
190 x 90 x 54 mm.
Weight
350g approx.
Martindale RC2000 warranty
Two-years.