The Martindale VI-15000 has a 1000V CATIV safety rating and LED indication for AC/DC voltages from 50V to 690V and above, ensuring compliance with health and safety recommendations for safe working in all BS EN61010 installation categories. It’s the simplest and most reliable way to ensure circuits have been de-energised and properly isolated prior to maintenance and modifications.
Based on the industry endorsed VI3800, the new CATIV design not only provides improved protection against voltage transients, but also includes a high wattage resistor that will limit the current in the event of damage to the cable in accordance with BS EN61243-3. The protection is built in where it’s needed, in the handheld probe assembly rather than just in the instrument providing superior protection for the user to other testers.
Fully compliant with HSE GS38 regulations, the VI-15000 comes complete with heavy duty two layer double insulated leads with a contrasting inner sheath to easily highlight cable damage. The tester features bright LEDs to clearly identify the voltage present in five levels with thresholds of up to 690V. The indicator, which requires no batteries, will identify both AC and DC sources and show polarity.
FEATURES
Supply powered AC/DC voltage indicator, no batteries required.
Extended voltage range to 1000V with bright LED indication.
Safety category CAT IV 1000V.
GS38 and BS EN61243-3:2010 compliant.
Heavy duty double insulated leads.
Polarity Indication.
Martindale VI-15000 Specifications
Electrical
Nominal Voltage Range
50 to 1000 V DC/AC RMS.
Nominal Voltage Threshold Indications
50, 120, 230, 400, 690 V AC/DC RMS.
Voltage Threshold Tolerance
Conforms to BS EN61243-3: 2010.
AC/DC Voltage Detection
Automatic.
Range Detection
Automatic.
Response Time
<0.1s.
Frequency Range
DC, 1 to 400 Hz.
Test Current
<3.5 mA at 1000 V AC/DC RMS.
Duty Ratio
30s ON (operated) / 240s OFF (recovery).
Environmental
Temperature and Humidity (Operating/Storage)
-10 to 55°C < 85% RH.
Altitude
Up to 2000m.
Pollution Degree
2.
Safety
Conformance
BS EN61343-3: 2010, CAT IV 1000 V
Class II, double insulation.
IP Rating
IP54 to BS EN60529.
General Specifications
Power
From circuit under test.
Dimensions
205 (L) x 67 (W) x 27 mm (D).
Weight
130g approx.
Martindale VI-15000 warranty
Two-years.
For more information on Martindale VI-15000 Voltage Indicator talk to Cuthbertson Laird Group