The Megger AVO410 is aimed at providing electricians with a rugged, easy to use multimeter for field use. Functions include voltage, current and resistance; in addition, there are extra functions that may also appeal to electrical and electronic engineers. The instrument features automatic or manual selection of ranges, True RMS readings and a CATIV 600 V safety rating.
The slim, compact case has a tough rubberised holster that provides that extra degree of protection from the extreme conditions found in industrial environments. The style of the AVO410 case and positioning of the function switch and buttons means the unit sits comfortably in the palm for single handed use.
FEATURES
6000 count backlit digital display.
True RMS reading on AC mode.
1000 V DC / 750 V AC ranges.
10 A AC / DC ranges.
Resistance, frequency and capacitance ranges.
CAT IV 600 V.
Megger Megger AVO410 Specifications
AC/DC Voltage
Range
DC Accuracy
AC Accuracy
600.0mV
+0.5% + 2 digits
50 Hz/60 Hz sine wave for 600.0 mV range, + (0.9% + 5 digits) 50 to 500 Hz *1
6.000V
60.00V
600V
DC 1000V / AC 750V
Overvoltage Protection
DC 1000 V or AC.
Input Impedance
10 MΩ // less than 100 pF.
CMRR (Common Mode Rejection Ratio/Normal Mode Rejection Ratio)
VAC: CMRR>60 dB at DC, 50 Hz/60 Hz.
VDC: CMRR > 10 dB at DC, 50/60 Hz.
NMRR: >50 dB at DC, 50/60 Hz.
AC Conversion Type
AC conversions are AC courple True RMS responding, calibrated to the sine wave input.
Note: *1 The basic accuracy is specified for a sine wave below 4000 counts. Over 4000 counts, add 0.6% to the accuracy. For non-sine waves below 2000 counts, refer to the following for accuracy: +1.5% addition error for C.F from 1.4 to 3.
Crest Factor
C.F = peak/rms.
AC/DC Current
Range
DC Accuracy
AC Accuracy
600.0 µA
+(1.0% + 2 digits)
N/A.
6000 µA
6.000 A
+(1.5% + 6 dgt) 50Hz - 500Hz *1
10.00 A
Overload Protection
A Input: 10 A (500 V) fast blow fuse.
µA Input: 600 V rms.
*1 AC Conversion Type: Conversion type and additional specification are the same AC/DC voltage.
Resistance
Range
Accuracy
Overload Protection
600.0 Ω * 2
+(0.7% + 2 digits)
600V rms.
6.000 kΩ
60.00 kΩ
600.0 kΩ
6.000 MΩ
+(1.0% + 2 digits)
60.00 MΩ * 1
+(1.5% + 2 digits)
*1 Less than 20 Hz, the sensitivity is 1.5 V rms.
*2 Max sensitivity <5 V AC rms.
Capacitance
Range
Accuracy
6.000 nF
+(1.9%) + 8 digits.
60.00 nF
600.0 nF
6.000 µF
60.00 µF
600.0 µF
6.00 mF*3
Overload Protection
600 V rms.
*3 <100 digit of reading rolling.
General Specifications
Display
6000 counts, updates 1.5/sec.
Polarity Indication
Automatic, positive implied, negative indicated.
Overrange Indication
"OL" or "-OL".
Low Battery Indication
Displayed when the battery voltage drops below operating voltage.
Auto Power Off
Approx 10 minutes.
Operating Conditions
Non-condensing ?10 °C,
11 °C ~ 30 °C (?80% R.H)
31 °C ~ 40 °C (?75% R.H),
41 °C ~ 50 °C (?45% R.H).
Storage Temperature
-20 to 60°C, 0 to 80% RH when battery removed from meter.
Temperature Coefficient
0.15 x (Spec.Acc'y) / °C, <18°C or >28°C.
Safety
IEC 61010 CAT IV 600 V.
Power Requirements
Standard 9 V battery: PP3, NEDA 1604, IEC6422 or JIS006P.
Battery Life
Alkaline: 300 hours.
Dimensions (W x H x D)
76 x 158 x 38 mm without holster.
82 x 164 x 44 mm with holster.
Weight
522g.
Megger AVO410 warranty
One-year (3 years upon registration).
For more information on Megger AVO410 Digital Multimeter talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.