The Megger B10E Power Supply Unit is used to supply voltage to the Circuit Breaker (CB) coils and spring-charging motor during installation and/or field service. Since the high-quality voltage available at the coil outputs is very load-independent, the power supplied resembles what is encountered under normal operating conditions. Circuit breaker functionality thus remains virtually unchanged. B10E enables you to test CB functions easily at the specified voltage levels.
The compact Power Supply Unit Megger B10E provides reliable assistance to those who do maintenance on high-voltage breakers. The control panel's intuitive layout makes it easy to operate, and the built-in thermal cutout and overload protector make it safe to use. The Megger B10E has been developed in collaboration with breaker manufacturers and testing personnel.
FEATURES
Reliable and stable power supply for circuit breaker testing.
Continuously variable 24-250 V AC or DC output.
Separate outputs for close coil, trip coil and spring charging motor voltage.
Direct triggering for minimum trip voltage testing.
Operate with a breaker analyser for efficiency in testing sequence.
Megger B10E Trip Coil Tester Specifications
Environment
Application field
For use in medium and high-voltage substations and industrial environments.
Operating temperature
0 to 50°C (32 to 122°F).
Storage
-40 to +70°C (-40 to +158°F).
Humidity
5% to 95% RH, non-condensing.
CE-Marking
LVD
2006/95/EC.
EMC
2004/108/EC.
General
Mains voltage
115 / 230 V AC, 50/60Hz.
Power consumption
3300W.
Protection
Thermal cut-outs, +80°C (+176°F)
Short-circuit protectors at DC outputs.
Display
LED.
Measurement - Voltmeter - digital
Range
0 - 300 V DC, 0 - 300 V AC.
Resolution
1 V.
Inaccuracy
+1% of displayed value, DC
+2.5% of displayed value, AC.
Current shunt
5 A / 50 mV +0.5% (built-in).
Test Lead Set, with 4mm Stackable Safety Plugs
2 x 0.25 m (0.8ft), 2.5 mm²
2 x 0.5 m (1.6ft), 2.5 mm²
8 x 2 m (6.6ft), 2.5 mm².
Dimensions
Instrument: 350 x 270 x 220 mm (13.8 x 10.6 x 8.7 inches)
Transport case: 610 x 290 x 360 mm (24.0 x 11.4 x 14.2 inches).
Weight
20.8 kg (45.8lbs)
29.3 kg (64.6lbs) with accessories and transport case.
Megger B10E warranty
One year.
Outputs (DC) CAT II
Coil, Closing/Breaking
Output Voltage
24-300 V DC
Load Interval
Max 1s (at currents over 50mA)
Ripple
2% peak-to-peak of the preset voltage
No-Load Voltage
Current
Load Dependency
24 V
10 A
<6%
48 V
10 A
<3%
110 V
7.9 A
<2%
250 V
3 A
<2%
300 V
1.25 A
<2%
Outputs (AC), CAT II
Coil, Closing/Breaking
Output Voltage
24 to 300 V AC
Load Current
Max 5 A
Load Interval
Max 30 min
Output DC, CAT II
Motor
Output Voltage
24 to 300 V DC (loaded)
Open Circuit Voltage
Current
Load Voltage
Max Load Interval
44 V
18 A
24 V
20s
48 V
12 A
40 V
60s
48 V
18 A
30 V
20s
120 V
12 A
90 V
60s
120 V
18 A
70 V
20s
240 V
6 A
200 V
60s
240 V
9 A
185 V
20s
Max Voltage: Terminals to Protective Earth (Ground)
Terminal
Voltage
Coil Closing, AC/DC
300 V AC
Coil Breaking, AC/DC
300 V AC
Motor
250 V AC
Shunt
250 V AC
Trigger Closing
250 V AC
Trigger Breaking
250 V AC
For more information on Megger B10E AC/DC Voltage Power Supply talk to Cuthbertson Laird Group