Sign In
The instrument featured on this page is the 230V model. If you require the 115V version please state at time of order.
The Megger CSU20A is a small light-weight current and voltage source primarily intended to work together with the SVERKER 750 Relay Testing Unit when testing differential relays. Besides testing differential relays the unit can be used as a multi-purpose AC/DC source.
Besides testing differential relays the unit can be used as a multi-purpose AC/DC source. The CSU20A features one AC current/voltage output, one fully rectified DC output and one half-wave rectified DC output for harmonic restraint testing.
Other features are a current measurement shunt, selectable current/voltage ranges and an AC mains input/output. Connecting the SVERKER 750/760 mains to the mains output of the CSU20A gives an in-phase synchronization of the two units.
Megger CSU20A Specifications
Output, AC
20A Setting
Output Voltage (min)
Load Time
Idle/Non-Load
26 V
Continuous
5 A
25 V
Continuous
10 A
22 V
Continuous
20 A
18 V
2 min
10A Setting
Output Voltage (min)
Load Time
Idle/Non-Load
52 V
Continuous
3 A
50 V
Continuous
5 A
47 V
Continuous
10 A
41 V
10 mins
Output, DC
DC Current
As above, less the voltage drop over the rectifying diodes.
General Specifications
Operating Temperature
-20 to +50°C (-4 to +122°F).
Mains Voltage
115 / 230 V AC, 50/60 Hz.
Thermal Protection
Built-In.
Current Measurements
Current shunt 0.1 A / 1 V, +2%.
Dimensions
280 x 178 x 246 mm (11” x 7” x 9.7”).
Weight
5.9 kg (13lbs) excluding transport case.
Megger CSU20A warranty
1 year.
For more information on Megger CSU20A Current and Voltage Source talk to Cuthbertson Laird Group
Enquire Now