The Megger CSU600AT high-current supply unit has two main fields of application. The first is to conduct primary tests on protective relays. A primary test shows whether all parts of the protection system are functioning together properly within the specified time limits under operating conditions. The second field of application involves conducting current tests on low-voltage circuit breakers and overcurrent devices.
It has a built-in timer and an analog ammeter that provide rough current settings quickly and easily. As a result, connection time has been reduced to the bare minimum.
FEATURES
Compact and rugged.
Quick and easy to use.
Broad application range.
Excellent weight/performance ratio.
Current Supply Units CSU600A/AT are used for:
Performance and transformation-ratio testing of current transformers.
Primary testing of relay-type cutouts.
Testing circuit breakers.
Commissioning of substation switchgear.
Outputs, AC, intermittent output1) (CAT I)
115 V Mains Voltage
230 V Mains Voltage
Current
Load time
Minimum Output Voltage
Load time
Minimum Output Voltage
0 A
Cont.
6 V
Cont.
9.5 V.
75 A
-
-
Cont.
9.3 V.
100 A
Cont.
5.6 V
1 hr
9.0 V.
200 A
15 mins.
5.3 V
5 mins.
8.5 V.
300 A
1.5 mins.
4.9 V
2 mins.
8.0 V.
400 A
1 min.
4.6 V
1 min.
7.5 V.
500 A
20 s.
4.2 V
30 s
7.0 V.
600 A
15 s.
3.9 V
20 s
6.5 V.
1) Maximum load time from cold state 25°C (77°F). Not valid for repeated tests.
Megger CSU600AT Specifications
Measurement section
Output for external ammeter
600/6 A.
Inaccuracy
+0.5%.
Timer (only CSU600AT)
Range
0-999.999 s.
Resolution
1 ms.
Inaccuracy
+0.02% of shown value + 0 to 2 ms.
Maximum cable lengths at 600 A
230 V mains
2 x 5 m (16 ft), 70 mm²
2 x 5 m (16 ft), 50 mm²
2 x 10 m (33 ft), 70 mm²
2 x 15 m (49 ft), 95 mm².
15 V mains
2 x 5 m (16 ft), 70 mm².
General Specifications
Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Specifications are subject to change without notice.
Operating temperature
0°C to +50°C (32°F to +122°F).
Storage temperature
-40°C to +70°C (-40°F to +158°F).
Humidity
5% - 95% RH, non-condensing.
CE-Marking
EMC: 2004/108/EC
LVD: 2006/95/EC.
Mains voltage
15 or 230 V AC, 50 / 60 Hz.
Power consumption (max)
115 V, 667 VA cont. (interm. 3738 VA)
230 V, 851 VA cont. (interm. 6440 VA).
Protection
Thermal cut-outs and miniature circuit breakers.
Dimensions
Instrument: 356 x 203 x 241 mm (14.0” x 8.0” x 9.5”)
Transport case: 610 x 290 x 360 mm (24.0 x 11.4 x 14.2”).
Current cables
2 x 5 m (16 ft), 50 mm².
Weight
21.9 kg (48 lbs) 38.3 kg (84.4 lbs) with accessories and carrying case.
Megger CSU600AT warranty
One year.