With ac and dc voltage measurements up to 1000 V and resistance measurements up to 20 MΩ, a non-contact voltage detection facility and a continuity buzzer with diode check, the Megger DCM330 is a truly versatile instrument. All of these features combined into a single compactinstrument eliminate the need for separate multimeter and clampmeter.
The Megger DCM330 is suitable for use anywhere where there is a requirement to measure ac current in single unshielded conductors less than 16mm diameter. Typical applications include domestic and industrial wiring installation fault-finding, basic load analysis, equipment commissioning and maintenance, machinery installations, etc.
FEATURES
200.0 A a.c. open-jaw current measurement.
0.1 V to 1000 V auto-ranging a.c. and d.c. voltage measurement.
0.1 Ω to 20.00 MΩ resistance range.
Continuity buzzer.
Diode check.
Non-contact detection of a.c. voltage.
CAT IV 600V.
Megger DCM330 Specifications
AC Current
Frequency
Range
Accuracy
50 - 60 Hz
0 - 200 A
+3% +3 digits.
Notes: Average sensing, RMS indicating. Overload protection: 400 A rms
AC/DC Voltage
Range
DC
AC
200 V
+1% + 2 digits
+1.5% + 5 digits.
1000 V
50 Hz - 500 Hz.
Resistance
Range
Accuracy
200 Ω
+1% + 5 digits.
2 kΩ
+1% + 2 digits.
20 kΩ
200 kΩ
2 MΩ
20 MΩ
+1.9% + 5 digits.
Diode check
mV: +1.5% +0.05 V
Overvoltage protection: 600 V rms.
Continuity
Buzzer operates: <50 br=""> Turns off: >250 Ω.
Response time: 0.25 sec - 1 sec
Display
3 1/2 digit large LCD
2000 countv Sample rate: 1.5/sec
Overrange: “OL”.
Auto power off
10 minutes after power on.
Battery
R03 UM4 AAA 1.5 V x 2 (not suitable for rechargeable cells)
Life: 250 hours (alkaline cells).
Operating temperature
0°C - 30°C (>80% RH).
Safety
IEC61010-1 1000 V CAT III
600 V CAT IV.
EMC
EN 61326-1.
Dimensions
54 mm (W) x 193 mm (H) x 31 mm (D).
Weight
280 g (battery installed).
Megger DCM330 warranty
One-year.
For more information on Megger DCM330 Fork multimeter talk to Cuthbertson Laird Group
Enquire Now