The Megger DET4TC2 is designed for extended temperature range use with an IP54 rated enclosure making it a genuinely outdoor instrument. The instrument provides all the functions required for ground system testing: variable frequency 2 pole, 3 pole, 4 pole, Attached Rod Technique (ART), stakeless, leakage current and ground noise voltage measurement.
The instrument is easy to use with a large rotary selector switch and one-press test button, both of which permit operation with gloved hands. Unlike some instruments, the design negates the need for a shorting link when making two pole measurements.
FEATURES
IP54 rated.
2, 3 and 4 point testing.
Attached Rod Technique (ART).
Stakeless measurements.
User selectable test frequency.
Dry cell or rechargeable versions.
User selectable output voltage.
Simple one button operation.
Robust carry case.
Backlit display.
Delivered with calibration certificate.
Megger DET4TC2 Specifications
Ingress Protection
IP54.
C Stake, P Stake and Noise Checks
Automatic.
Noise Rejection
40 V peak to peak.
2 wire, 3 wire and 4 wire tests
Yes with no shorting links required.
No disconnect testing (ART)
Yes, with ICLAMP.
Stakeless Measurements
Yes, with ICLAMP and VCLAMP.
Instrument Output
Voltage: +25 V or +50 V at 94 Hz, 105 Hz, 111 Hz and 128 Hz
Current: 4.5 mA or 0.45 mA or 0.045 mA.
Ground Current Range with Clamp
0.5 mA to 19.9 A.
Ground Current Accuracy
5% +3 digits.
Ground Voltage Range
0 to 100 V AC.
Ground Voltage Accuracy
2% +2 V.
Resistance Range
0.01 Ω to 200 kΩ.
Resistance Accuracy
2P measurements: 2% +3 digits
3P measurements: 2% +3 digits
4P measurements: 2% +3 digits
ART measurements: 5% +3 digits
Stakeless measurements: 7% +3 digits.
Maximum Probe Resistance
Rp limit: 200 kΩ (50 V output voltage)
Rc limit: 200 kΩ (50 V output voltage)
Limits reduced to 100 kΩ for 25 V output voltage
Limits reduced to 5 kΩ for 0.01 Ω resolution.
Display
31?2 digit high contrast liquid crystal, backlit.
Battery Type
DET4TC2: 8 off AA (LR6) cells
DET4TCR2: 8 off AA (LR6) NiMH rechargeable cells.
Operating Temperature Range
-15 °C to +55 °C / 5 °F to 131 °F.
Storage Temperature Range
-40 °C to +70 °C / -40 °F to 158 °F.
Safety
Complies with the requirements of IEC 61010-1 100V CAT IV
between terminal pairs.
EMC
In accordance with IEC61326-1.
Standards Compliance
Complies with the requirements of KEMA K85B
Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems
up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective
measures”.
Part 1 - General requirements
Part 5 - Resistance to earth.
Dimensions
203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in).
Weight
1kg (2.2lb).
For more information on Megger DET4TC2 Digital Ground Tester talk to Cuthbertson Laird Group
Enquire Now