Sign In
NB: This version of the Megger DLRO10HD (1001-453) is not supplied with test leads.
Equally at home in the laboratory, the workshop or in the field, on the bench or on the ground, Megger’s heavy duty DLRO10HD low resistance ohmmeter combines rugged construction with accuracy and ease of use. It features an internal rechargeable battery and can also operate from a mains supply, even if the battery is completely flat.
The Megger DLRO10HD is well suited to measuring thick conductors, bonds and quality of welding because of its 10 A range for resistance values up to 250 mΩ. The instrument provides five test modes each of which is selected through a simple rotary control.
The five operating modes include two automatic modes that sense connection of the probes to minimise test time and increase productivity. To overcome thermal EMFs current is passed through the unit under test in both directions and the resulting resistance averaged.
FEATURES
Interchangeable test lead terminations.
High or low output power selection for condition diagnosis.
Rechargeable battery or line power supply, continuous operation, even with dead battery.
10 A for 60 seconds, less time waiting to cool, great for charging inductance.
High input protection to 600 V, inadvertent connection to line or UPS voltage will not blow a fuse.
Heavy duty case: IP 65 lid closed, IP54 operational (battery operation only).
Rotary switch selects one of five test modes, including auto start on connection.
Although the DLRO10HD is not designed as transformer ohmmeter, it is fitted with a test in progress lamp associated with the TEST button, which indicates that current is flowing in the C1-C2 loop. This lamp and a warning triangle on the LCD will flash at end of a test on an inductive load whilst a discharge current is still flowing and will stop flashing when the current has decayed to less than 1 mA.
Megger DLRO Comparison Chart
FEATURE
DLRO10
DLRO10HD
DLRO10X
DLRO10HDX
Power limited output test ranges (<0.25 W)
High power output test ranges (25 W)
Auto current reversal
Auto start (continuity detection)
High input protection
Noise immunity specified at 100 mV
Noise limit exceeded indicator
User interchangeable detachable battery pack
Hang from neck operation
Operate from mains supply
IP65 lid closed
IP54 in use
Ultra tough case
Test result storage
Printer and PC output
User selectable test limits
DLRO10 HD Product Video
Megger DLRO10HD Specifications
Test Current
Resistance Range
Resolution
Basic Accuracy*
Full Scale Voltage
Max. Power Output
0.1 mA
0 to 2500.0 Ω
0.1 Ω
+ 0.2%
25 mV
25 µW
0.1 mA
0 to 250.00 Ω
0.01 Ω
+ 0.2%
25 mV
2.5 µW
1 mA
0 to 25.000 Ω
1 mΩ
+ 0.2%
25 mV
25 µW
10 mA
0 to 2500.0 mΩ
0.1 mΩ
+ 0.2%
25 mV
250 µW
100 mA
0 to 250.00 mΩ
0.01 ?Ω
+ 0.2%
25 mV
2.5 mW
1 A
0 to 25.000 mΩ
1 ?Ω
+ 0.2%
25 mV
25 mW
10 A
0 to 2500.0 ?Ω
10 ?Ω
+ 0.2%
25 mV
0.25 W
1 A
0 to 2500.0 mΩ
0.1 mΩ
+ 0.2%
2.5 V
2.5 W
10 A
0 to 250.00 mΩ
0.01 ?Ω
+ 0.2%
2.5 V
25 W
* The accuracy stated assumes forward and reverse measurements.
Temperature coefficient
< 0.01% per °C, from 5 °C to 40 °C
Display size/type
Main 5 digit + 2 x 5 digit secondary displays.
Battery type
6 V, 7Ah sealed lead acid.
Voltage input range
100 - 240 V 50 / 60 Hz 90 VA.
Charge time
8 hours.
Backlight
LED Backlight.
Battery life
>1000 Auto (3 sec) tests.
Auto power down
300s.
Operating temperature and humidity
-10 °C to +50 °C.
EMC
In accordance with IEC61326-1 (Heavy industrial).
Maximum lead resistance
100 mΩ total for 10 A operation irrespective of battery condition.
Mode selection
Rotary switch.
Range selection
Rotary switch.
Pouch for test leads
Yes (lid mounted).
IP rating
IP65 case closed, IP54 battery operation.
Dimensions
(L)315 mm x (W)285 mm x (H)181 mm.
Weight
6.7 kg.
Megger DLRO10 HD warranty
Two years.
For more information on Megger DLRO10HD - No Lead Set talk to Cuthbertson Laird Group