Sign In
The Megger DPM1000 power clamp meter combines the functionality of power meter, harmonics meter and data logger in one easy-to-use package. The design meets the requirements of BSEN 61010-1 CAT IV 600 V for supply side applications. A large, backlit LCD clearly displays all measurements that can be selected at the touch of a button or when rotating the selection dial. It also automatically switches off to save battery consumption.
The DPM1000 can measure DC, AC, pulsed and mixed currents up to 1000 A simply by clamping the jaws around the appropriate conductor, whilst voltages up to 1000 V AC or DC may be measured by the supplied test leads, Where power measurements are to be made both techniques above are performed simultaneously. All power related parameters including energy consumption, frequency, total harmonic distortion, distortion factor and capacitance. It features auto-ranging and has 3 phase rotation indication.
The DPM1000 measures Single and 3 phase active power and power factor, the harmonic content of the signal, up to the 25th harmonic can be displayed. Temperature measurements can be made up 1000°C using the thermocouple provided.
The DPM 1000 may be used to perform data logging to its internal non-volatile memory. You can record a maximum of 9999 readings/records to the memory over a period of time and download the data to produce graphs and reports.
FEATURES
AC/DC Voltage to 1000V.
AC/DC Current to 1000A.
True RMS Resistance 100kΩ.
LCD Display.
Phase rotation indication.
Inrush peak current.
Auto backlight display.
Frequency measurement.
Capacitance measurement.
Power Factor Measurement.
Watt measurement to 1MW.
Harmonic measurement.
Harmonic distortion.
Diode test.
Non-contact volt alert.
Continuity Beeper.
Data Hold/Min-Max/Peak Hold.
Bright LED torch.
Temperature to 1000° C.
CAT IV 600V Rating.
Bluetooth/Megger Link APP.
Megger DPM1000 Specifications
AC Current
Range
100A - 1000A.
Resolution
0.01A.
Basic Accuracy
+ (1.5% +5d) at 50-500Hz.
Conversion Type
AC+DC True-RMS.
AC Voltage
Range
10V - 1000V.
Resolution
0.01V.
Basic Accuracy
+ (1.5% +5d) at 50-500Hz.
Input Impedance
3.5MΩ.
Overload Protection
1000V rms.
DC Current
Range
100A - 1000A.
Resolution
0.01A.
Basic Accuracy
+ (1.5% +5d).
DC Voltage
Range
100V - 1000V.
Resolution
0.01V.
Basic Accuracy
+ (0.7%+2d).
Input Impedance
3.5MΩ.
Overload Protection
1000V rms.
AC+DC Voltage
Range
100V - 1000V.
Resolution
0.01V.
Basic Accuracy
+ (1.7%+7d).
Input Impedance
3.5MΩ.
Overload Protection
1000V rms.
Watt
Range
10KW - 1MW.
Resolution
1W.
Power Factor
Range
-1.00 - 1.00.
Resolution
0.01.
Basic Accuracy
+ 5d.
T.H.D.
Range
0.1% - 100%.
Resolution
0.1%.
Basic Accuracy
+ (3.0%+10d).
Harmonics
Resolution
0.1%.
Basic Accuracy
+ (5.0%+10d) For order 1-12
+ (10.0%+10d) For order 13-25.
Resistance
Range
1kΩ - 100kΩ.
Resolution
0.01Ω.
Basic Accuracy
+ (1.0% + 5dgt).
Overload Protection
1000V rms.
Continuity Beeper
Range
<30Ω, 2.KHz tone buzzer.
Diode Test
Open Circuit Voltage
+ 1.8 V max.
Capacitance
Range
4µF - 4000µF.
Resolution
1nF.
Basic Accuracy
+ (1.9%+8d).
Overload Protection
1000V rms.
Frequency Counter
Range
20.00Hz ~ 10.00KHz.
Resolution
0.01Hz.
Accuracy
+ 0.5%+3d.
Temperature
Range
-50°C ~1000°C.
Resolution
0.1°C.
Accuracy
+ (1.0%+3°C).
Overload Protection
1000V rms.
General Specifications
Sampling Rate
times/sec.
Overload Indication
“OL” or “-OL”.
Operating Temperature
0°C~50°C, ?80% RH.
Storage Temperature
- 10°C ~ 50°C.
International Standard
IEC/EN 61243-3:2014.
Safety Standard
IEC 61010-1, Designed to meet
UL61010 Spec CAT IV 600V, CAT III 1000V.
Maximum Conductor Size
40mm.
Maximum Busbar Size
61 x 12mm.
Power
AAA Size Battery 1.5V x 6.
Battery Life
50 hrs.
Dimensions
103mm(W) x 258mm (L) x 55mm(H).
Weight: (with battery)
600g.
For more information on Megger DPM1000 Power Clamp Meter talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.