The Megger Egil with PC comes with a USB interface for communication with a PC and the CABA Win™ Circuit Breaker Analysis Software.
The Egil is intended for use on circuit breakers with one contact per phase. EGIL incorporates features commonly found on more complex test systems, but is designed to be smaller, simpler to use and less expensive than other similar test sets. If the main contacts are equipped with parallel pre-insertion resistor contacts, the Megger Egil automatically records the difference between main and resistor contacts. Auxiliary contact timing as well as coil current traces are recorded.
The Megger EGIL is equipped with a connector marked USB. The EGIL can be connected to a computer in which the CABA Breaker Analysis program has been installed. This enables you to: store settings and test parameters for individual breakers in the computer; make quick evaluations and comparisons; print out reports; store test results in the computer.
It’s price makes it attractive to smaller utilities and it is an ideal supplementary product for maintenance departments at larger power companies and for testing contractors.
The EGIL is intended primarily for testing high-voltage circuit breakers at medium-level voltages. There must not, however, be more than one break per phase since the time channels are not galvanically isolated. Contact times are recorded for main contacts, pre-insertion resistor contacts and auxiliary contacts. Coil currents are also recorded.
Coil currents are measured automatically and presented together with other readings immediately after testing on the display window or via the built-in printer. EGIL is easy to use - a built-in sequencer (program unit) sets the instrument automatically for the next sequential breaker operation.
Intended primarily for measuring travel (motion), the optional analog input channel finds many other uses as well. If this channel is not installed, all associated menu commands are hidden. A Megger EGIL with the SDRM option together with the SDRM accessory enables static and dynamic resistance measurements.
FEATURES
Suitable for testing timing and travel on all circuit breakers with single interrupter per phase.
Extremely easy-to-use and reliable.
Two separate timing channels for measurement of auxiliary contacts.
Analog measurement channels for travel transducers or general voltage/current measurements.
Static and dynamic resistance measurements along with the SDRM201 optional accessory.
Megger Egil Specifications
Environment
Application field
For use in medium and high-voltage substations and industrial environments.
Operating temperature
-10°C to +50°C (14°F to +122°F).
Storage
-40°C to +70°C (-40°F to +158°F).
Humidity
5% - 95% RH, non-condensing.
CE-Marking
LVD
2006/95/EC.
EMC
2004/108/EC.
General Specifications
Mains voltage
115/230 V AC (switchable), 50/60 Hz.
Display
LED.
Mains voltage
115/230 V AC (switchable), 50/60 Hz.
Power consumption
100 VA (max).
Time measurement
Measurement time: 1 to 100 s
Resolution: 0.1 to 10 ms.
Number of channels
3 with common ground.
Time base inaccuracy
0.05% of the reading + resolution.
Status thresholds
Closed: < 10 Ω + 20%
Resistor: 10 Ω + 20% to 3 kΩ +20%
Open: > 3 kΩ + 20%.
Open circuit voltage
24 V + 20%.
Short circuit current
100 mA + 20%.
AUX 1 & 2
Number of channels: 2, galvanically isolated.
Contact-sensing (Dry)
Status thresholds
Closed
< 600 Ω + 30%.
Open
> 600 Ω + 30%.
Open circuit voltage
20 V + 20% DC.
Short circuit current
25 mA + 20%.
Voltage sensing (Wet)
Status thresholds
Open indication
< 8 V (polarity insensitive).
Close indication
> 13 V (polarity insensitive).
Working voltage
250 V AC/DC.
Current measurement
Range: + 25 A per channel.
Resolution: 25 mA.
Inaccuracy: 1% of the reading +100 mA.
Working voltage: 250 V AC / DC.
Breaker operation
Sequences: C, O, C-O, O-C, O-C-O.
Continuous current
5 A.
Max current
25 A during 300 ms, rest time 1 min.
Contact function
Two independent control functions.
Contact characteristics
Non bouncing, closing time max. 0.1 ms.
Make/Break capacity
25 A, 250 V (AC or DC) per contact function.
Start breaker operation
By rotary switch.
Pulse length
Adjustable in steps of 10 ms.
Pulse delay
Adjustable in steps of 10 ms.
Working voltage
250 V AC / DC.
Printout
Type of printout: Graphic and numeric.
Printer
Thermal printer with fixed print head.
Graphic resolution
8 dots/mm - 203 dpi.
Paper width
114 mm (4.5”).
Available languages
English, German, French, Spanish, Swedish.
Dimensions
Instrument: 360 x 210 x 190 mm (14.2” x 8.3” x 7.5”)
Transport case: 420 x 300 x 230 mm (16.5” x 11.8” x 9.0”).
Weight
6.3 kg (14 lbs)
10 kg (22 lbs) with accessories and transport case.
Megger Egil warranty
One year.
For more information on Megger Egil with PC talk to Cuthbertson Laird Group