Sign In
The Megger LTW325 Loop Impedance Tester is three phase safe and category IV 300V rated, making it suitable for use on supplies from 50V to 300V AC single phase, as well as on 440V three phase installations.
Megger Loop Impedance Testers use the latest digital processing techniques to separate the test signal from the fundamental frequency of the supply. This means the Megger LTW325 automatically averages a large number of results over the duration of the test. This enables non trip testing to be performed without DC injection, a technique which is, in any case, proving ineffective with electronic RCDs.
FEATURES
2 Wire Non-tripping loop tester.
50 V to 440 V operation.
110 V centre-tap loop testing.
CATIV installation testing.
AUTO start - operation.
0.01 Ω resolution.
Megger LTW Summary Chart
Function
LTW315
LTW325
LTW335
LTW425
2-Wire Non Tripping Loop Testing
2-Wire Fast Test (High Current)
110V to 280V Applications
50V to 440V Applications
-
Phase to Phase Testing
-
20KA PFC Range
40KA PFC Range
-
-
-
0.01Ω Resolution
0.001Ω Resolution
-
-
-
AUTO Noise Detection
AUTO Start Loop Test
Voltage Measurements
Frequency Measurements
Max Zs Display
-
R2+R2 Display
-
Backlit Display (White Light)
Built-In Front Cover (Foldaway)
IP54 Weatherproof Case
Accepts Rechargeable Batteries
Test Result Storage
-
-
-
Downloading Test results
-
-
-
Test Lead Set with Crocs
Mains Socket Test Lead
Full Calibration Certificate
Megger LTW325 Specifications
Accuracy
All accuracy statements are based on:
Ambient Temperature
23° +2°C.
Nominal Voltage Source
230 V a.c +1%.
Voltage Measurements
(ac only)
50 V to 440 V.
Accuracy
+2% +1 V.
Frequency Measurements
Range
25 Hz to 99.99 Hz.
Accuracy
+0.1 Hz.
A warning will be shown if applied voltage exceeds 440 V.
Damage will occur if applied voltage exceeds 600 V rms.
Loop Testing Accuracy
+5% +0.03 Ω
@230 V a.c.
+10% +0.03 Ω
@100 V a.c and 280V.
+10% +0.03 Ω
@100 V a.c and 300V a.c.
+15% +0.03 Ω
@50 V a.c.
No Trip Loop and High Current Loop Test
Source Voltage
50 V to 440 V (49 Hz to 50.1 Hz).
Display Range
0.01 to 2000 Ω.
Accuracy
+5% + 0.03 Ω.
No Trip Loop Test Nominal Current
15 ma (at nominal 230 V a.c supply).
High Current Loop Test
4 A (at nominal 230 V a.c supply).
Operational Range
0.30 to 1000 Ω.
Prospective Fault Current (PFC)
Prospective Fault Current
=Measured Source Voltage/Loop Resistance.
Maximum Range
No Trip Mode: 20 KA.
Accuracy is derived from loop test and voltage measurement.
Safety
IEC 61010
Designed to IEC61010-1
Designed for 300 volts to Earth Category IV
with phase to phase voltages to 440V.
Fuse protected to 600 volts rms AC.
EN61557
Complies with the following parts of EN61577:
Electrical Safety in Low Voltage Systems up to
1000V ac and 1500V dc - Equipment for testing,
measuring or monitoring of protective measures:
Part 1: General Requirements.
Part 3 - Loop Resistance
E.M.C
In accordance with IEC61326-1.
Power Supply
Battery
8 x 1.5V Cells IEC LR6 Type (AA Alkaline).
Rechargeable
8 x 1.2V NiCd or NIMH Cells.
Battery Life
2000 consecutive tests.
Mechanical
Weight
1000g +10% excluding test leads.
Dimensions
203 x 148 x 78 mm.