Sign In
Offering CAT IV, the Megger MIT1025 is a compact, light 10 kV insulation resistance tester for the diagnostic testing and maintenance of high voltage electrical equipment. Enclosed in a tough case it is both smaller and lighter than its predecessor (MIT 1020), making it even easier to carry and store. As well as measuring insulation resitance to 20 TΩ, the Megger MIT1025 also offers various diagnostic tests such as Polarisation index, Dielectric Absorption Ratio, Step Voltage, Dielectric discharge and ramp testing.
Advanced memory storage includes time/date stamping of results, logging of data and recall of results to screen. A fully isolated USB device interface is used for safe transfer of test records to all versions of Megger’s data management.
The Megger MIT1025 can be powered from the mains supply or by it’s rechargeable battery, which provides for 4½ to 6 hours of continuous testing with a 100 MΩ load, depending on model.
The battery pack contains Lithium-ion cells and should be replaced when it no longer holds a charge. A new battery is available as a spare part from Megger. The battery pack is housed within a grey moulded cover secured by four screws. On no account must the transparent inner case be opened. Hazardous voltages up to 10kV will be exposed.
FEATURES
Measures up to 35 TΩ.
Safety rated up to CAT IV 1000 V to 3000 m.
Unique dual-case design - additional user protection.
Operates from battery or AC mains supply.
Rapid charge Li-ion battery.
Advanced memory with time/date stamp.
MIT515, MIT525 & MIT1025 Intro and Demo
Megger MIT1025 Specifications
Voltage Input Range
85-265 V rms, 50/60 Hz, 60 VA.
Battery
11.1 V, 5.2 A hour, meets IEC 62133:2003.
Battery Life
Typical capacity 4.5 hours continuous at 10 kV with a 100 MΩ load.
Battery Charge Time
2.5 hours from deep discharge,
2 hours normal discharge.
30 Min. Quick Charge
1 hour operation at 5 kV, 100 MΩ.
Test Voltages
500 V, 1000 V, 2500 V, 5000 V, 10000 V.
User Defined Test Voltage
5 kV to 10 kV in 25 V steps.
Accuracy (23 °C)
+5% to 2 TΩ, +20% to 20 TΩ.
Guard
2% error guarding 500 kΩ leakage with 100 MΩ load.
Display Range Analogue
100 kΩ to 10 TΩ.
Display Range Digital
10 kΩ to 20 TΩ.
Short Circuit Current
3 mA nominal, max. power on all loads outperforming many 5 mA testers.
Insulation Alarm
10 kΩ to 1 TΩ.
Capacitor Charge
<5 s/µF at 3 mA to 10 kV.
Capacitance Range (above 500V)
10 nF to 25 µF (dependant on measurement voltage).
Capacitance Accuracy
+10% +5 nF.
Voltage Output Accuracy (0 to 30°C)
+4%, -0%, +10 V nominal test voltage at 1 GΩ.
Current Measurement Range
0.01 nA to 6 mA.
Current Measurement Accuracy (23°C)
+5% +0.2 nA at all voltages.
Interference (Noise) Rejection
1 mA per 600 V up a maximum of 3 mA.
Voltmeter Range
30 V to 660 V ac or dc, 50/60 Hz.
Voltmeter Accuracy
+3%, +3 V.
Timer Range
Up to 99 minutes, 15 second minimum setting.
Memory Capacity
5.5 hours continuous logging every 5 second intervals.
Test Regimes
IR, IR(t), DAR, PI, SV, DD, ramp test.
Interface
USB type B (device).
Real Time Output
USB, 1 reading/second (voltage, current and resistance).
Environmental
Altitude
3000 m, CAT rating maintained
>2000 m*
* Test leads connected.
Operating Temperature
-20 °C to 50 °C.
Storage Temperature
-25 °C to 65 °C.
Humidity
90% RH non-condensing at 40 °C.
Ingress Protection
IP65 (lid closed), IP40 (lid open).
General Specifications
Safety
Meets the requirements of IEC 61010-1, CATIV 600 V.
EMC
Meets the requirements of IEC61326-1
Dimensions
315 x 285 x 181mm.
Weight
4.5kg.
Megger MIT1025 Warranty
2 year.
HV Lead Sets
Accessory
Order Code
HV TEST LEAD SETS (MIT525 only)
5m lead set, large size insulated clips (3 x leads).
1005-259
10 m lead set, large size insulated clips (3 x leads).
1005-260
15 m lead set, large size insulated clips (3 x leads).
1005-261
3 m lead set, medium size insulated clips (3 x leads).
1005-262
10 m lead set, medium size insulated clips (3 x leads).
1005-263
HV TEST LEAD SETS (MIT525 only)
3 x 5 m with large insulated clips.
1002-645
3 x 8 m with large insulated clips.
1002-646
3 x 10 m with large insulated clips.
1002-647
3 x 15 m with large insulated clips.
1002-648
3 x 5 m with medium insulated clips.
1002-641
3 x 8 m with medium insulated clips.
1002-642
3 x 10 m with medium insulated clips.
1002-643
3 x 15 m with medium insulated clips.
1002-644
SCREENED HV TEST LEAD SETS (MIT515, MIT525, MIT1025 only)
3m, 15kV screened, large size insulated clips, supplied in carry holdall.
1005-266
10m, 15kV screened, large size insulated clips, supplied in carry holdall.
1005-267
15m, 15kV screened, large size insulated clips, supplied in carry holdall.
1005-268
20m, 15kV screened, large size insulated clips, supplied in carry holdall.
1005-269
For more information on Megger MIT1025 10kV Insulation Tester talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.