Sign In
The Megger MIT400 mk2 series insulation and continuity testers are designed not just for Electrical and Industrial, but with an exceptionally wide range of applications from electrical installations, cable testing, motor testing, automotive, ESD, panel building, avionics, maintenance etc.
The stabilised insulation test voltage is now accurate to +2% -0%. This compares to the industry standard +20%, providing a more accurate test voltage without the risk of over-voltage damage to circuits or components. The output voltage is maintained between 0 & 2% throughout the test range.
The MIT410/2 adds additional features required for engineers working on more demanding applications. Functions such as PI and DAR, capacitance measurement and a greater range of test voltages increase the suitability for applications such as manufacturing/production testing, panel building, railway and other transportation, motor testing, cable inspection/quality control, street lighting maintenance, avionics ground testing and maintenance, military applications.
DUAL DIGITAL DISPLAY
Large main digital readout for good visibility of all main measurement results.
Second digital display for additional data such as:
Insulation test voltage.
Insulation leakage current.
Supply frequency (when measuring volts).
Test mode eg. PI, DAR or t ( t = Timer mode).
FEATURES
Stabilised insulation testing.
Auto hold on continuity tests.
Analogue arc with pointer.
200Gohm test range.
Continuous continuity range.
Rechargeable options.
Contoured ergonomic design.
Increased battery life.
IP54 ingress protection.
CAT IV safety design.
600V measurement.
Specification Summary table
MIT400/2
MIT410/2
MIT420/2
MIT430/2
Insulation
50/100 V
-
250/500/1000 V
Variable
-
-
PI-/DAR/Timed
-
Lock Button on MΩ
Continuity
Continuity 0.01 Ω to 1 MΩ
100 Ω
Auto Reverse Polarity (setup ON-OFF)
-
Lead Null (<10 Ω)
Voltage
AC/DC Volts 600 V
mV AC/DC Range
Frequency Measurements 15 to 400 Hz
-
Input Impedance
0.25 MΩ
0.25 MΩ
0.25 MΩ
0.25 MΩ
Capacitance
Capacitance 0.1 nF to 10 µF
-
-
Other Features
PASS/FAIL on Limit Alarms
-
Auto Power Down (setup)
On-Board Memory
-
-
Bluetooth Download + Software
-
-
-
AA Alkaline or NIMH
Both
Both
Both
Both
Recharger Ready
-
-
-
CAT IV 600V / CAT III 1000V
Megger MIT400/2 Series Specifications
Test Voltage
MIT 400/2
250, 500 and 1000 V.
MIT 410/2, 420/2 and 430/2
50, 100, 250, 500 and 1000 V.
Insulation Accuracy
Test Voltage
Range
Accuracy
50 V
10 GΩ
+2% + 2 digits + 4.0% per GΩ.
100 V
20 GΩ
+2% + 2 digits + 2.0% per GΩ.
250 V
50 GΩ
+2% + 2 digits + 0.8% per GΩ.
500 V
100 GΩ
+2% + 2 digits + 0.4% per GΩ.
1000 V
200 GΩ
+2% + 2 digits + 0.2% per GΩ.
Display Range
Analogue
1 GΩ full scale.
Resolution
0.1 kΩ.
Short Circuit/Charge Current
2 mA +0% to -50% to EN 61557-2 (2007).
Open Circuit Voltage Insulation
-0 +2% +2 V.
Test Current
1 mA at min pass value of insulation to a max of 2 mA max.
Leakage
10% + 3 digits.
Voltage
3% +3 digits +0.5% of rated voltage.
Timer Control
60 second countdown timer.
Note: Above specifications only apply when high quality silicone leads are being used.
Continuity
Continuity Measurement
0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale).
Continuity Accuracy
+ 3% + 2 digits (0 to 100 Ω )
+5% +2 digits (100 to 500 kΩ)
(500 kΩ to 1 MΩ unspecified)
Service Error: BS EN 61557-4 (2007) - + 2.0%, 0.1 Ω - 2 Ω + 6.8%.
Open Circuit Voltage
5V +1 V.
Test Current
200 mA (-0 mA to +20 mA)
(0.01 Ω to 4 Ω).
Polarity
Single polarity (default) / Dual polarity (configurable on setup).
Lead Resistance
Null up to 9.00 Ω.
Voltage
Voltage Range
AC: 10mV to 600V RMS sinusoidal (15Hz to 400Hz)
DC: 0 to 600V.
Volt Range Accuracy
AC: +2% +1 digit
DC: +2% +2 digit
Service Error: BS EN 61557-1 (2007) - + 2.0% + 2d,
0 V - 300 V AC/DC + 5.1%.
Waveform
Unspecified range: 0 - 10 mV (15 to 400 Hz)
For non-sinusoidal waveforms additional specifications apply.
Non-sinusoidal waveforms: +3% + 2 digits >100 mV to 600 V TRMS
+8% + 2 digits 10 mV to 100 mV TRMS.
Frequency
Frequency Measurement Range
15 Hz to 400 Hz.
Frequency Measurement Accuracy
+0.5% +1 digit (100 Hz to 400 Hz unspecified).
Capacitance Measurement (MIT420/2 and MIT430/2)
Capacitance Measurement
1 nF to 10 µF.
Capacitance Measurement Accuracy
+5.0% + 2 digits (0.1 nF to 1 nF unspecified).
Storage (MIT420/2 and MIT430/2)
Storage Capacity
>1000 test results.
Data Download
Bluetooth wireless
Bluetooth Class II.
Range
Up to 10m.
General Specifications
Battery Life
3000 insulation tests with duty cycle of 5 seconds ON/55 sec off @ 1000 V into 1 MΩ.
Dimensions
Instrument: 228 x 108 x 63 mm (9.00 x 4.25 x 2.32 inches).
Weight
600g (MIT400/2) (1.32lbs).
For more information on Megger MIT410/2 Insulation and Continuity Tester talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.