Sign In
The MIT400 mk2 series insulation and continuity testers are designed not just for Electrical and Industrial, but with an exceptionally wide range of applications from electrical installations, cable testing, motor testing, automotive, ESD, panel building, avionics, maintenance etc.
All primary results are displayed in the larger digital display and repeated on the analogue arc. Auxiliary test information such as frequency, leakage current, insulation or circuit voltage is displayed in the smaller secondary digital display.
The MIT430/2 has a tough shock-absorbing rubber over moulding that provides excellent grip, and it also features weatherproof IP54 protection. In addition, the instrument has a bar at the top to allow the addition of future accessories, such as magnetic hanging straps and belt loops.
ELECTROSTATIC DISCHARGE TESTING
The ability to swap displays from kΩ, MΩ, GΩ to 10^5, 10^6, 10^7 and to vary the test voltage make the MIT430/2 ideal for ESD testing, including servicing of equipment and routine maintenance of ESD conductive flooring, bench mats and grounding systems etc. Typical industries include: electronic manufacturing, electronic servicing and repair calibration houses.
FEATURES
Stabilised insulation testing.
Variable 50V to 1000V test voltage.
Auto hold on continuity tests.
Analogue arc with pointer.
200Gohm test range.
Continuous continuity range.
Rechargeable options.
Contoured ergonomic design.
Increased battery life.
IP54 ingress protection.
CAT IV safety design.
600V measurement.
Specification Summary table
MIT400/2
MIT410/2
MIT420/2
MIT430/2
Insulation
50/100 V
-
250/500/1000 V
Variable
-
-
PI-/DAR/Timed
-
Lock Button on MΩ
Continuity
Continuity 0.01 Ω to 1 MΩ
100 Ω
Auto Reverse Polarity (setup ON-OFF)
-
Lead Null (<10 Ω)
Voltage
AC/DC Volts 600 V
mV AC/DC Range
Frequency Measurements 15 to 400 Hz
-
Input Impedance
0.25 MΩ
0.25 MΩ
0.25 MΩ
0.25 MΩ
Capacitance
Capacitance 0.1 nF to 10 µF
-
-
Other Features
PASS/FAIL on Limit Alarms
-
Auto Power Down (setup)
On-Board Memory
-
-
Bluetooth Download + Software
-
-
-
AA Alkaline or NIMH
Both
Both
Both
Both
Recharger Ready
-
-
-
CAT IV 600V / CAT III 1000V
Megger MIT400/2 Series Specifications
Test Voltage
MIT 400/2
250, 500 and 1000 V.
MIT 410/2, 420/2 and 430/2
50, 100, 250, 500 and 1000 V.
Insulation Accuracy
Test Voltage
Range
Accuracy
50 V
10 GΩ
+2% + 2 digits + 4.0% per GΩ.
100 V
20 GΩ
+2% + 2 digits + 2.0% per GΩ.
250 V
50 GΩ
+2% + 2 digits + 0.8% per GΩ.
500 V
100 GΩ
+2% + 2 digits + 0.4% per GΩ.
1000 V
200 GΩ
+2% + 2 digits + 0.2% per GΩ.
Display Range
Analogue
1 GΩ full scale.
Resolution
0.1 kΩ.
Short Circuit/Charge Current
2 mA +0% to -50% to EN 61557-2 (2007).
Open Circuit Voltage Insulation
-0 +2% +2 V.
Test Current
1 mA at min pass value of insulation to a max of 2 mA max.
Leakage
10% + 3 digits.
Voltage
3% +3 digits +0.5% of rated voltage.
Timer Control
60 second countdown timer.
Note: Above specifications only apply when high quality silicone leads are being used.
Continuity
Continuity Measurement
0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale).
Continuity Accuracy
+ 3% + 2 digits (0 to 100 Ω )
+5% +2 digits (100 to 500 kΩ)
(500 kΩ to 1 MΩ unspecified)
Service Error: BS EN 61557-4 (2007) - + 2.0%, 0.1 Ω - 2 Ω + 6.8%.
Open Circuit Voltage
5V +1 V.
Test Current
200 mA (-0 mA to +20 mA)
(0.01 Ω to 4 Ω).
Polarity
Single polarity (default) / Dual polarity (configurable on setup).
Lead Resistance
Null up to 9.00 Ω.
Voltage
Voltage Range
AC: 10mV to 600V RMS sinusoidal (15Hz to 400Hz)
DC: 0 to 600V.
Volt Range Accuracy
AC: +2% +1 digit
DC: +2% +2 digit
Service Error: BS EN 61557-1 (2007) - + 2.0% + 2d,
0 V - 300 V AC/DC + 5.1%.
Waveform
Unspecified range: 0 - 10 mV (15 to 400 Hz)
For non-sinusoidal waveforms additional specifications apply.
Non-sinusoidal waveforms: +3% + 2 digits >100 mV to 600 V TRMS
+8% + 2 digits 10 mV to 100 mV TRMS.
Frequency
Frequency Measurement Range
15 Hz to 400 Hz.
Frequency Measurement Accuracy
+0.5% +1 digit (100 Hz to 400 Hz unspecified).
Capacitance Measurement (MIT420/2 and MIT430/2)
Capacitance Measurement
1 nF to 10 µF.
Capacitance Measurement Accuracy
+5.0% + 2 digits (0.1 nF to 1 nF unspecified).
Storage (MIT420/2 and MIT430/2)
Storage Capacity
>1000 test results.
Data Download
Bluetooth wireless
Bluetooth Class II.
Range
Up to 10m.
General Specifications
Battery Life
3000 insulation tests with duty cycle of 5 seconds ON/55 sec off @ 1000 V into 1 MΩ.
Dimensions
Instrument: 228 x 108 x 63 mm (9.00 x 4.25 x 2.32 inches).
Weight
600g (MIT400/2) (1.32lbs).
For more information on Megger MIT430/2 Insulation and Continuity Tester talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.