Sign In
The Megger MOM200A is designed to check and measure contact resistances in highvoltage circuit breakers, disconnecting switches (isolators) and busbar joints. This unit is an excellent choice when 200 amperes or less are needed for measurement.
The MOM200A is ideal for finding poor connections since it can put out 100A for extended periods. Its range extending up to 20 milliohms makes it ideal for measuring many different types of connections.
FEATURES
Measures contact resistance in circuit breakers, disconnecting switches, busbar connections, safety devices, etc.
Easy to operate.
Designed for rugged field use.
Highly flexible cable connections.
Portable and lightweight, weighs only 14 kg (31 lbs).
Megger MOM200A Specifications
Specifications are avalid at nominal input voltage and an ambient temperature of +25°C (77°F). Specifications are subject to change without notice.
Environment
Application Field
Intended for use in high voltage substations and industrial environments.
Operating Temperature
0 to 50°C (32 to +122°F).
Storage and Transport Temperature
-40 to +70°C (-40 to +158°F).
Humidity
5 to 95% RH, non-condensing.
CE-Marking
EMC
2004/108/EC.
LVD
2006/95/EC.
General
Mains Voltage
230 V AC, 50/60Hz (optional 115V version available).
Power Consumption
1610 VA (max).
Protection
Miniature circuit breakers, thermal cutouts.
Instrument Dimensions
280 x 178 x 246 mm (11 x 7 x 9.7 inches).
Transport Case Dimensions
560 x 260 x 360 mm (22 x 10.2 x 14.2 inches).
Weight
14.6 kg (32.2lbs)
26 kg (54.1lbs) with accessories and transport case.
Current Cables
2 x 5 m (16ft), 25 mm².
Sensing Cables
2 x 5 m (16ft), 2.5 mm².
Measurement Section
Resistance
Range
0 to 1999 µΩ
0 to 19.99 mΩ.
Resolution
1 µΩ
10 µΩ.
Inaccuracy
+1% of reading + 1 digit.
Output
Current
0 to 200 A.
Open Circuit Voltage
4.7 V DC.
Current Shunt Output
10 mV/100 A +0.5%, max 20 mV out, max 10 V to protective earth (ground).
Max Load Capacity (Current Adjustment Set to 100%)
Output Current 100 A DC
Minimimum Output Voltage
3.8 V DC.
Max Load Time
5 min or 15 min.
Rest Time
15 min or 60 min.
Output Current 200A DC
Minimum Output Voltage
3.0 V DC.
Max Load Time
20 seconds.
Megger MOM200A warranty
One-year.
For more information on Megger MOM200A Micro_Ohmmeter talk to Cuthbertson Laird Group