The Megger PAM420, provides phase angle measuring functionality identical to that of the PAM410, but adds facilities for two-channel voltage, current and frequency measurement.
It also has a high-accuracy timing function that can be triggered by voltage signals or volt-free contacts, and can measure times up to 999.999 s with a resolution of 1 ms. The PAM420 has a built-in rechargeable battery, allowing it to be used in almost any location.
The PAM420 is suited for checking polyphase metering installations, testing protective relays, make comparative test in electrical substations, and verifying the phase angle deviation on power transformers.
FEATURES
Phase Angle Meter.
2 channels: voltage, current and frequency meter.
Timer.
Compact and lightweight.
Local calibration.
Rechargeable batteries.
Easy to use.
Megger PAM420 Specifications
Measurement Section
Current - Inputs I1 and I2
Measurement category
CAT III 500 V
CAT IV 300 V.
Input range
0 - 25 A AC.
Inaccuracy
0.5% of reading.
Resolution
0.1 A.
Protection
Built-in 25 A fuse.
Voltage - Inputs U1 and U2
Measurement category
CAT III 500 V
CAT IV 300 V.
Input range
0 - 500 V AC true RMS.
Inaccuracy
0.15 % of reading + 0.03% of range (+ 0.15 V).
Resolution
0.1 V.
Phase Angle
Phase angle range
0 - 359.9° (2-500 V and 0.15-25 A.
Type of phase angle measurement
Current-current, voltage-voltage and current-voltage.
Waveform
Sinusoidal.
Resolution
0.1 V.
Inaccuracy
+0.5° at >10% of voltage/current range
+1° at 2-10% of voltage/current range
+2° at 1-2% of voltage/current range.
Frequency
Note: Frequency component in voltage component only.
Range
15 - 75 Hz.
Inaccuracy
0.1%.
Resolution
0.01 Hz.
Timer
Measurement category
CAT II 250 V.
Range
0-999.999 s.
Resolution
1 ms.
Inaccuracy
+0.02% + 2 digits of displayed value.
Max input voltage
250 V AC / DC.
Input debouncing filter
1 ms.
Temperature
Operating
-10°C to +50°C (14°F to +122°F).
Storage & transport
-20°C to +70°C (-4°F to +158°F).
Humidity
5% - 95% RH, non-condensing.
CE-Marking
LVD
2006/95/EC.
EMC
2004/108/EC.
General
Display
Alpha numerical LC display with backlighter.
Measurement category
CAT III 500 V
CAT IV 300 V.
Enclosure class
IP21.
Power supply
Rechargeable batteries.
Mains adapter
100 - 240 V AC, 50 / 60 Hz
Adapter output voltage: 9 V DC
Power consumption: 10 W (max).
Dimensions
Instrument: 260 x 140 x 55 mm (except handle), (10.2” x 5.5” x 2.2”)
Transport case: 390 x 300 x 140 mm, (15.4” x 11.8” x 5.5”).
Weight (with accessories and transport case)
1.2 kg (2.6 lbs)
3.5 kg (7.7 lbs).
Megger PAM420 warranty
1 year.