Sign In
The low-cost entry-level RCDT310 model is suitable for use on supplies between 100V and 280V, and offers 0.5I, I and 5I tests, with provision for tests starting at 0?/180? of the supply waveform, as well as for DC tests.
It also has facilities for testing standard and selective RCDs, and covers current ranges from 30mA to 500mA. When connected to a live supply, it defaults to voltmeter mode.
Even if they are inadvertently connected to a live three-phase supply, RCD testers in Megger’s RCDT300 range remain undamaged, and present no safety hazard to the user. Introduced after extensive customer research into the requirements of electrical contractors, these innovative instruments combine rugged construction with straightforward operation, and they are offered at very competitive prices.
FEATURES
Tests standard, DC and selective RCDs.
Ramp testing.
Auto (Remote) testing.
3 Phase safe.
Enables testing on 110 V centre tapped supplies.
Weatherproof to IP54.
Megger RCDT310 Specifications
RCD Test Ranges (to EN61557-6)
Supply Voltage
RCDT310: 100 V to 280 V (45 Hz to 65 Hz)
RCDT320: 50 V to 280 V (45 Hz to 65 Hz)
RCDT330: 50 V to 280 V (45 Hz to 65 Hz)
Minimum voltage 71 V for 300 mA RCDs, 100 V for 500 mA RCDs and 205 V for 1000 mA RCDs.
Test Current Accuracy
No Trip Test
(1/2I): -8 to -2%.
Trip Test
(I, 5I): +2% to +8%.
Trip Time
+1% + 1 ms.
Voltage Measurement
AC Range
0 to 300 V (25 to 450 Hz).
Accuracy
+2% + 2 digits.
Frequency Measurements (RCDT320/330 Only)
Range
25 to 450 Hz.
Accuracy
25 to 199.9 Hz + 0.1 Hz
200 Hz to 450 Hz + 1 Hz.
Fault (Touch) Voltage
Displayed Range
0 to 50 V.
Error
+5%/+15% + 0.5 V.
Programmable RCD Step Increments
10 mA to 50 mA
1 mA steps.
50 mA to 500 mA
5 mA steps.
500 mA to 1000 mA
10 mA steps.
Test Result Storage (1000 Results) - RCDT330 Only
Job Number
256 locations.
Distribution Board Number
99 locations.
Circuits
99 locations.
Phases
P1, P2, P3.
Temperature and Humidity
Operating Range
-5 to 40°C.
Operating Humidity
93% RH at +40°C max.
Storage Range
-25 to 70°C.
Maximum Altitude
2000m.
Environmental Protection
IP54.
Safety
Rating
IEC 61010-1 CAT III 300 V phase to earth.
Power Supply
Batteries
8 x 1.5 V cells IEC LR6 type (AA alkaline).
Rechargeable
8 x 1.2 V NiCd or NiMH cells.
Battery Life
2000 consecutive tests.
General Specs
Weight
980g.
Dimensions
203 x 148 x 78 mm.
E.M.C
In accordance with IEC61326-1.
Megger RCDT310 warranty
Three-years.
For more information on Megger RCDT310 RCD Tester talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.