Sign In
The Megger RCDT330 covers a wider supply voltage range of 50V to 290V than the RCDT310, allowing use with centre-tapped 110V supplies. It incorporates ramp testing testing, for RCD tripping current measurement, and the unique Megger auto sequence test feature, which saves time by allowing the tester to conduct all the RCD tests, and to store the results while the operator stands by the RCD, resetting it as appropriate.
The operating current range of the RCDT330 covers 10mA to 1,000mA devices, and the ability to measure AC supply voltage and frequency. The large liquid crystal display for test results is backlit in this model, making it easier to use in locations with low ambient light levels. Data is stored in non-volatile memory, being retained when the instrument is switched off or batteries are exhausted.
FEATURES
Tests standard, DC and selective RCDs.
Ramp testing.
Auto (Remote) testing.
3 Phase safe.
Enables testing on 110 V centre tapped supplies.
Tough rubber armoured case with built-in cover.
Weatherproof to IP54.
Megger RCDT330 Specifications
RCD Test Ranges (to EN61557-6)
Supply Voltage
RCDT310: 100 V to 280 V (45 Hz to 65 Hz)
RCDT320: 50 V to 280 V (45 Hz to 65 Hz)
RCDT330: 50 V to 280 V (45 Hz to 65 Hz)
Minimum voltage 71 V for 300 mA RCDs, 100 V for 500 mA RCDs and 205 V for 1000 mA RCDs.
Test Current Accuracy
No Trip Test
(1/2I): -8 to -2%.
Trip Test
(I, 5I): +2% to +8%.
Trip Time
+1% + 1 ms.
Voltage Measurement
AC Range
0 to 300 V (25 to 450 Hz).
Accuracy
+2% + 2 digits.
Frequency Measurements (RCDT320/330 Only)
Range
25 to 450 Hz.
Accuracy
25 to 199.9 Hz + 0.1 Hz
200 Hz to 450 Hz + 1 Hz.
Fault (Touch) Voltage
Displayed Range
0 to 50 V.
Error
+5%/+15% + 0.5 V.
Programmable RCD Step Increments
10 mA to 50 mA
1 mA steps.
50 mA to 500 mA
5 mA steps.
500 mA to 1000 mA
10 mA steps.
Test Result Storage (1000 Results) - RCDT330 Only
Job Number
256 locations.
Distribution Board Number
99 locations.
Circuits
99 locations.
Phases
P1, P2, P3.
Temperature and Humidity
Operating Range
-5 to 40°C.
Operating Humidity
93% RH at +40°C max.
Storage Range
-25 to 70°C.
Maximum Altitude
2000m.
Environmental Protection
IP54.
Safety
Rating
IEC 61010-1 CAT III 300 V phase to earth.
Power Supply
Batteries
8 x 1.5 V cells IEC LR6 type (AA alkaline).
Rechargeable
8 x 1.2 V NiCd or NiMH cells.
Battery Life
2000 consecutive tests.
General Specs
Weight
980g.
Dimensions
203 x 148 x 78 mm.
E.M.C
In accordance with IEC61326-1.
Megger RCDT330 warranty
Three-years.
For more information on Megger RCDT330 RCD Tester talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.