Sign In
The Megger S1-1568 15 kV insulation resistance tester has been designed, specified and tested to meet the stringent requirements of power utilities in the 21st century. In addition to being tough, high performance insulation testers the S1-1568 Megger offers the ability to perform accurate insulation resistance measurements in extreme, high noise environments, rapid charging of cable capacitance, and even remote operation for both convenience and safety.
The Megger S1-1568 test set combines class-leading noise rejection of 8 mA - twice that of most comparable instruments - with user selectable software filtering and the ability to make accurate and dependable measurements up to 35 TΩ.
A valuable additional feature of the S1-1568 is provision for remote control via a fully isolated USB port. This, together with provision for internal storage of date- and time-stamped results, makes the instruments well suited for use in production environments. Stored results can be recalled to the display, downloaded via a Bluetooth wireless link or accessed via the USB port.
FEATURES INCLUDE:
Resistance measurement: 15 TΩ - 5 kV, 35 TΩ - 10 kV, 35 TΩ - 15 kV.
High current - 6 mA short circuit current.
High noise immunity - 8 mA of noise rejection.
Four software filters: 10s, 30s, 100s, 200s.
Li-ion battery - charges in 2 hours and gives up to 6hours continuous testing.
CATIV 600 V safety rating up to 3000m.
CATIV 1000 V safety rating up to 4000m.
Remote operation via USB cable.
Download of memory via isolated USB cable Bluetooth®.
IR, timed IR, DAR, PI, DD, SV and ramp diagnostic tests.
Large LCD display with backlight.
Dedicated voltmeter function (30 V to 660 V) AC or DC.
Advanced memory, on screen recall and real time clock for date/time stamped results.
PowerDB Lite asset management software.
Option to record temperature and/or relative humidity with saved results (measured independently).
The Tester meets EN 61557 Parts 1 and 2; and EN 61010-1, CAT IV 600 V Pollution Degree 2 standards. CAT IV equipment is designed to protect against transients from the primary supply level, such as an electricity meter or an overhead or underground utility service.
Megger S1-Series Accuracy
MODEL S1-568
5000V
2500V
1000V
500V
250V
+5% to
1 TΩ
500 GΩ
200 GΩ
100 GΩ
50 GΩ
+20% to
10 TΩ
5 TΩ
2 TΩ
1 TΩ
500 GΩ
MODEL S1-1068
10KV
5000V
2500V
1000V
500V
+5% to
2 TΩ
1 TΩ
500 GΩ
200 GΩ
100 GΩ
+20% to
20 TΩ
10 TΩ
5 TΩ
2 TΩ
1 TΩ
MODEL S1-1568
15KV
10KV
5000V
2500V
1000V
+5% to
3 TΩ
2 TΩ
1 TΩ
500 GΩ
200 GΩ
+20% to
30 TΩ
20 TΩ
10 TΩ
5 TΩ
2 TΩ
Megger S1-Series Specifications
AC Voltage (auto ranging)
S1-568, S1-1068
90 - 264 V rms, 50/60 Hz, 100 A.
S1-1568
90 - 264 V rms, 50/60 Hz, 200 A.
Battery Life
S1-568
6 hours (typical) continuous testing at 5 kV with a 100 MΩ load.
S1-1068
4.5 hours (typical) continuous testing at 10 kV with a 100 MΩ load.
S1-1568
4.5 hours (typical) continuous testing at 15 kV with a 100 MΩ load.
30 min quick charge
1 hour operation at 5 kV with a 100 MΩ load.
Charge Time
2.5 hours deep discharge, 2 hours normal discharge.
Test Voltage
250 V, 500 V, 1000 V, 2500 V, 5000 V, 10000 V, 15000 V.
Lock Test Voltage
40 V to 1 kV in 10 V steps
1 kV to 5 kV in 25 V steps
5 kV to 15 kV in 25 V steps.
Test voltage Accuracy
+4%, -0%, +10 V nominal test voltage at 1 GΩ load (0°C to 30°C
Resistance Range
10 k to 15 TΩ @ 5 kV
10 k to 35 TΩ @ 10 kV
10 k to 35 TΩ @ 15 kV.
Display Range Analogue
100 kΩ to 10 TΩ.
Display Range Digital
10 kΩ to 35 TΩ.
Short Circuit/charge Current
6 mA.
Insulation Test Alarm
100 kΩ to 10 GΩ.
Capacitor Charge (on battery)
< 2.5 s/µF to 5 kV
< 5 s/µF to 10 kV
< 6.3 s/µF to 15 kV. Capacitor Charge (with AC) < 1.5 s/µF to 5 kV
< 2.7 s/µF to 10 kV
< 4 s/µF to 15 kV. Capacitance Capacitor Discharge 5 kV to 50 V :< 120 ms/µF
10 kV to 50 V:< 250 ms/µF
15 kV to 50 V:< 3500 ms/µF. Capacitance Range With test voltage set above 500 V. S1-568: 10 nF to 25 µF
S1-1068: 10 nF to 25 µF
S1-1568: 10 nF to 50 µF. Capacitance Measurement With test voltage set above 500 V. S1-568: 10 nF to 25 µF
S1-1068: 10 nF to 25 µF
S1-1568: 10 nF to 50 µF. Capacitance Measurement Accuracy 10 nF to 10 µF : +10% +5 nF. Current Range 0.01 nA to 6 mA. Current Accuracy +5% +0.2 nA at all voltages (23 °C). Voltmeter Range 30 V to 660 V ac or dc, 45Hz - 65Hz. Timer Range Up to 99 minutes 59 seconds 15 second minimum setting. Memory Capacity 1 hrs logging @ 5 sec intervals. Test Modes IR, IR(t), DAR, PI, SV, DD, ramp test. Interface USB type B (device), Bluetooth® Class 2. Real Time Output (V, I, R) readings at a rate of 1 Hz. Remote Control Remote control via USB cable only (requires RC dongle to be in position). Environmental Operating Temperature -20 °C to 50 °C. IP Rating IP65 (lid closed), IP40 (lid open). Safety Meets the requirements of IEC 61010-1 CATIV 600 V to 3000 m (5 kV, 10 kV) CATIV 1000 V to 4000 m (15 kV). EMC Meets the requirements of IEC61326-1. Dimensions & Weight Dimensions S1-568, S1-1068: 285 mm x 181 mm x 315 mm S1-1568: 305 mm x 194 mm x 360 mm. Weight S1-568, S1-1068: 4.5 kg S1-1568: 6.5 kg. Megger S1-1568 warranty Two-year.
< 5 s/µF to 10 kV
< 6.3 s/µF to 15 kV. Capacitor Charge (with AC) < 1.5 s/µF to 5 kV
< 2.7 s/µF to 10 kV
< 4 s/µF to 15 kV. Capacitance Capacitor Discharge 5 kV to 50 V :< 120 ms/µF
10 kV to 50 V:< 250 ms/µF
15 kV to 50 V:< 3500 ms/µF. Capacitance Range With test voltage set above 500 V. S1-568: 10 nF to 25 µF
S1-1068: 10 nF to 25 µF
S1-1568: 10 nF to 50 µF. Capacitance Measurement With test voltage set above 500 V. S1-568: 10 nF to 25 µF
S1-1068: 10 nF to 25 µF
S1-1568: 10 nF to 50 µF. Capacitance Measurement Accuracy 10 nF to 10 µF : +10% +5 nF. Current Range 0.01 nA to 6 mA. Current Accuracy +5% +0.2 nA at all voltages (23 °C). Voltmeter Range 30 V to 660 V ac or dc, 45Hz - 65Hz. Timer Range Up to 99 minutes 59 seconds 15 second minimum setting. Memory Capacity 1 hrs logging @ 5 sec intervals. Test Modes IR, IR(t), DAR, PI, SV, DD, ramp test. Interface USB type B (device), Bluetooth® Class 2. Real Time Output (V, I, R) readings at a rate of 1 Hz. Remote Control Remote control via USB cable only (requires RC dongle to be in position). Environmental Operating Temperature -20 °C to 50 °C. IP Rating IP65 (lid closed), IP40 (lid open). Safety Meets the requirements of IEC 61010-1 CATIV 600 V to 3000 m (5 kV, 10 kV) CATIV 1000 V to 4000 m (15 kV). EMC Meets the requirements of IEC61326-1. Dimensions & Weight Dimensions S1-568, S1-1068: 285 mm x 181 mm x 315 mm S1-1568: 305 mm x 194 mm x 360 mm. Weight S1-568, S1-1068: 4.5 kg S1-1568: 6.5 kg. Megger S1-1568 warranty Two-year.
For more information on Megger S1-1568 15kV Insulation Resistance Tester talk to Cuthbertson Laird Group
Enquire Now