The Megger TTRU3 ratio meter test set is a fully automatic, self-checking, menu-driven turns ratiometer. The test set measures the turns ratio, vector relationship, excitation current as well as transformer diagnostic health indicators of power, distribution, and instrument transformers. The design of this instrument is such that it operates properly, independent of line voltage quality and frequency. This allows use of any generator driven power source of 500W or higher.
The TTRU3 is designed to test ALL power, instrument, and distribution transformers without the need of traditional high voltage excitation. With our patent pending step up technique, you are no longer required to know the “proper” test voltage to apply to obtain a “good” result - the test set decides for you - all in a box that is up to 35% smaller and lighter than other turns ratio meters.
With 3ø excitation, testing is up to five times faster than previous phase-by-phase switching single instruments, and errors due to loading of delta secondary and tertiaries are problems of the past.
The test set can be used to test single-phase and three-phase transformers, both with and without taps in accordance with the requirements of the IEEE C57.12.90 - 2013 and IEC 60076-1 standards. For three-phase measurements, the test set is connected to all three phases of the transformer to be tested. The TTRU3 applies all three phases simultaneously which permits automatic measurement of all phases without changing connections.
The TTRU3 is also designed to operate single phase on three phase transformers to help isolate transformer phase related issues. The TTRU3 measures turns ratio, phase deviation and excitation current readings which are displayed on the built in 7 inch color display or customer PC.
Unlike other transformer ratiometers, the TTRU3 operates in both step up and step down ratio mode. Step down ratio excites the primary and measures the induced voltage on the secondary, while step up excites the secondary and measures the induced voltage on the primary.
FEATURES
3ø test voltage - fast testing of all transformers.
Patent pending 3ø Step Up Testing.
Confirm expected nameplate vector configuration.
Ability to measure actual vs expected phase shift.
Unique kelvin clamps with adjustable 3-inch jaw.
Banana plug input for connection to terminal blocks.
Turns ratio % error vs nameplate with pass/fail.
PC interface via USB for remote control operation and downloading of test results.
Megger TTRU3 Product Video
TTRU3 Selection Guide
MODEL
TTRU3EXP
TTRU3PRO
TTRU3ADV
Max Turns Ratio
50,000 Down / 200 Up
50,000 Down / 200 Up
50,000 Down / 100 Up
Max Induced Voltage
250 V
250 V
125 V
ø Shifting TX’s Measurement
up to 50,000 records and 2,000 photos
up to 10,000 records
up to 2,000 records
Magnetic Balance
Optional
Optional
Printer
Optional
Optional
Power DB Control
Optional
Optional
Clone facility to set up multiple testers
Optional
Optional
Megger TTRU3 Specifications
Input Power
90-264 VAC, 47-63 Hz, 250 VA Max.
Output
Voltage
3ø, 1-48 VAC, up to 250 V on Primary.
Frequency
50-480 Hz.
Current
0.1 mA - 1 A, Max 1 A @ 48 V.
Turns Ratio Measurement Methods
3ø Step Up
3ø Step Down
1ø Step Up
1ø Step Down.
Turns Ratio Range and Accuracy - Guaranteed accuracy from -20°C to +50°C.
Step Down Excitation
25-48 V
+0.05% 0.8 - 1000
+0.10% 1001 - 2000
+0.30% 2001 - 15000
+1% 15001 - 50000.
1-24 V
+0.10% 0.8 - 1000
+0.20% 1001 - 2000
+0.60% 2001 - 15000.
Step Up Measurement
25-250 V
+0.05% 0.8 - 200 (most Power Tx).
1-24 V
+0.10% 0.8 - 200.
Excitation Current Measurement
Resolution
0.1 mA 0.1 mA - 100 mA - 1 mA 101-1000 mA.
Accuracy
+ 1% +0.1 mA.
Frequency Measurement
Resolution
0.1 Hz.
Accuracy
+0.1% +0.1 Hz.
Transformer Phase Measurement
Range
0 - 360 Degrees.
Accuracy
+ 0.05 Degrees.
General Specifications
Operating Temperature
-20°C to +50°C (-4°F to +122°F).
Storage Temperature
-30°C to +70°C (-22°F to +158°F).
Relative Humidity
0-90%, non-condensing.
Safety
IEC 61010-1:2010 + AMD1:2016.
EMI/EMC
IEC 61326-1:2012.
RoHS2
EN50581.
Display
180mm (7 in.)
800 x 480 Resolution
1100 NITS.
Transformer Testing Standards
IEEE C57.152-2013
IEC 60076-1:2011
AS/NZS 6076 1:2014
CIGRE 445 2011.
Internal/External Data Storage
Up to 2000 sets of 3 phase results internal storage
Transferable via USB 2.0/3.0 thumb drive.
Communication/Control Software
180mm (7in) built it display running custom GUI
USB Interface for PC Control running custom GUI.
Printer Output
51mm (2in) thermal printer
Prints all measurement data displayed on GUI.
Case
Ruggedized case with fold out feet
Canvas carrying bag for leads and accessories.
Weight
6.5 Kg (14lbs).
Dimensions
406 x 304 x 254mm (16 x 12 x 8in.)
Megger TTRU3 warranty
One-year.