Sign In
When a vacuum circuit breaker is commissioned or undergoes routine tests, it is very important to be able to ascertain whether or not the Vacuum Interrupter (VI) is intact before putting it back into operation.
The VI in vacuum breakers do not last forever. Leakage starts after years or decades and the interrupters fill with air making the breaker unreliable. In most cases, the leakage process is rapid once it has started. In addition to leakage, dirt on the poles and on the exterior surface of the interrupter can make it unsafe during operation. The mechanics of the breaker can become misaligned so that the distance between the poles no longer is adequate. The Megger VIDAR (introduced in 1985 as the Programma Vidar), uses high voltage DC to test the integrity of vacuum breakers.
The Megger VIDAR enables you to check the integrity of the vacuum interrupter quickly and conveniently by means of the known relationship between the flashover voltage and the vacuum interrupter. A suitable test voltage (DC) is applied to the breaker, and the result is known immediately.
The VIDAR permits you to select among test voltages from 10 to 60 kV DC. One of these voltages is customised and specified by the customer when ordering A green lamp indicates approval of the VI. A red lamp indicates that it is defective. Two-hand control and a high-voltage warning lamp enhances safety.
FEATURES
Tests the integrity of vacuum interrupters quickly, safely and easily.
User defined voltage selection.
Extensive voltage range.
Easy to operate. Follows ANSI/IEEE standardized DC test methods.
Lightweight and portable.
Megger Vidar Product Video
Megger Vidar Specifications
Environment
Application field
For use in medium and high-voltage substations and industrial environments.
Operating temperature
-10°C to +50°C (14°F to +122°F).
Storage
-40°C to +70°C (-40°F to +158°F).
Humidity
5% - 95% RH, non-condensing.
CE-Marking
LVD
2006/95/EC.
EMC
2004/108/EC.
General Specifications
Mains voltage
115/230 V AC (switchable), 50/60 Hz.
Power consumption
69 VA (max).
Green lamp
Indicates an approved breaking chamber.
Red lamp
Indicates a defect breaking chamber, lights up if the current exceeds 0.3 mA.
Yellow lamp
Indicate that the test was interrupted.
Standard voltages, switchable
10, 14, 25, 40 and 60 kV DC.
Accuracy
0 to -15%.
Customised voltage
Between 10 and 60 kV DC. Determined at the factory. Default voltage is 50 kV.
Ripple
Max 3%.
Dimensions
Instrument: 250 x 210 x 125 mm (9.8” x 8.3” x 4.9”)
Transport case: 460 x 430 x 210 mm (18.0” x 17” x 8.3”).
Weight
6.9 kg (15.5 lbs)
10.7 kg (23.6 lbs) with accessories and transport case.
Megger Vidar warranty
One year.
For more information on Megger Vidar Vacuum Interrupter Tester talk to Cuthbertson Laird Group
Enquire Now