Find The Needle Add My Company
Metrel MI 3122 SMARTEC Z Line Loop RCD
The MI 3122 SMARTEC Z Line-Loop / RCD is designed specifically for live circuit testing. The instrument contains integrated characteristics of fuses and RCDs for the evaluation of test results. The online voltage monitoring system allows the operator to control what is happening on three simultaneous voltages in real-time. The bright red and green PASS / FAIL lights and help screens for each measurement make the handling of the instrument easy and clear. All the results can be quickly saved on the instrument and then downloaded via the optional A 1291 EuroLink PRO or A 1290 EuroLink PRO Plus software for evaluation and professional report generation after testing. The MI 3122 SMARTEC Z Line-Loop / RCD performs RCD, loop, line, AC voltage, frequency and phase sequence tests required by the EN 61557 standard. FEATURES Supports all live tests on LV-electrical circuits: - Loop impedance / prospective fault current - Line impedance / prospective short-circuit current Built- in fuse characteristics for quick evaluation of measuring results. RCD tests (trip out time, contact voltage, ramp test, Autotest). Testing on 1- and 3-phase systems. Phase sequence test. Metal test button for touch voltage detection. High accuracy non tripping loop test for RCD protected circuits. Pre-programmed limits. PASS/FAIL evaluation of measurement result. Bright GREEN/RED indicators provides visual evaluation of results. Suited for testing on CAT IV installations. Magnetic holder allowes hands-free operation. Built-in battery charger. Two level memory structure for saving of test results and parameters. Basic downloading with EuroLink PRO PC SW package. Compatible with EuroLink PRO Plus PC SW package. USB and RS232 ports. Metrel MI 3122 Technical Specifications RCD Testing Nominal Residual Current (A, AC) 10mA, 30mA, 100mA, 300mA, 500mA, 1000mA Test Current Shape Sine-Wave (AC), Pulsed (A) RCD Type G (non-delayed), S (time-delayed) Test Current Starting Polarity 0 or 180° Voltage Range 50V ? 264V (45Hz ? 65Hz) Complete measuring range corresponds to EN 61557 requirements Contact Voltage Measuring Range (V) Resolution (V) Accuracy 0.0 ? 19.9 0.1 (-0%/+15%) of reading + 10 Digits 20.0 ? 99.9 0.1 (-0%15%) of reading Test Current: max 0.5xl?N Limit Contact Voltage: 25V, 50V Trip-Out Time Measuring Range (ms) Resolution (ms) Accuracy 0 ? 300 1 +3ms Test Current: 1/2 x l?N, l?N, 2xl?N, 5xl?N Trip-Out Current Measuring Range (l?) Resolution (l?) Accuracy 0.2xl?N ? 1.1l?N (AC Type) 0.05l?N +0.1xl?N 0.2xl?N ? 1.5l?N (A Type, IDN30mA) 0.05l?N +0.1xl?N 0.2xl?N ? 2.2l?N (A Type, IDN <30mA) 0.05l?N +0.1xl?N Fault Loop Impedance (no disconnecting device or FUSE selected) Measuring range according to EN 61557 is 0.25Ω ? 9.99kΩ Measuring Range (Ω) Resolution (Ω) Accuracy 0 ? 9.99 0.01 +(5% of reading + 5 digits) 10 ? 99.9 0.1 +(5% of reading + 5 digits) 100 ? 999 1 +10% of reading 1k ? 9.99k 10 +10% of reading Test Current (at 230V): 6.5A (10ms Nominal Voltage Range: 30V ? 65Hz)

For more information on Metrel MI 3122 SMARTEC Z Line Loop RCD talk to Cuthbertson Laird Group

Enquire Now

  Please wait...

Location for : Listing Title