Sign In
Metrel MI 3155 plus the METREL A 1532 Electric Vehicle Adaptor
The A 1532 EVSE (Electric Vehicle Supply Equipment) adapter is a special accessory intended for testing Electric Vehicle Supply Equipment (EVSE) together with supported METREL installation testers. The A 1532 is intended for testing Mode 3 EV supply equipment with a type 2 connector.
To choose the MI 3155 + A 1532 Adpt please select the option in the dropdown above the price.
The A 1532 is supported with the Metrel MI 3155.
The Metrel MI 3155 EurotestXD is the newest flagship of Metrel’s most advanced line of multi-functional measuring instruments and is designed specifically for testing in industry.
What differentiates this instrument from the rest is its ergonomic design and an intuitive user interface, encompassing a memory organizer and fully programmable AUTO SEQUENCEs, managed through a large colour touch screen display.
It is fully compliant with functionality standards (e.g. IEC/EN 61557) and other reference standards for testing (e.g. IEC/EN/HD 60364-4-41,...) as is required for any instrument that performs TRMS current measurements, RCD tests, line and loop impedance tests with 3 (and 4) wires and earth resistance measurements.
Besides those, the instrument supports a wide range of tests and measuring functions, including on-line voltage monitoring, phase sequence testing, varistor testing, PI/DAR calculation, luminance measurement, discharge time testing, ISFL measurements, IMD tests as well as functional and visual inspections.
MEASURING FUNCTIONS
Live Transformer’s Impedance Measurement with Four Wire Test.
Hi-precision Short Circuit Current evaluation with Calculated Hot factor.
3-wire test of PE (RPE function) without extension lead conductor.
Autotest insulation function between L-N, N-PE and L-PE (R ISO ALL function).
4 wire continuity test.
Insulation resistance with DC voltage from 50 V to 2500 V and PI, DAR calculation.
Varistor test.
Continuity of PE conductors with 200 mA DC test current with polarity change.
Continuity of PE conductors with 7 mA test current without RCD tripping.
2-wire and 3-wire high-current loop impedance (L-PE) measurement.
3-wire loop impedance (L-PE) measurement with Trip Lock RCD function.
Touch voltage / Contact voltage measurement with external P/S probe.
2-wire and 3-wire line impedance (L-L, L-N) measurement.
1-phase / 3-phase TRMS voltage and frequency measurements.
Line, loop and RCD measurements at frequency range 16 ... 400 Hz.
Phase sequence.
Power and THD measurement (up to the 12th harmonic).
RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S).
Earth resistance (3-wire and 2-clamps method).
Specific earth resistance with Ro-adapter (option).
TRMS leakage and load currents (option).
First fault leakage current (ISFL).
Testing of Insulation Monitoring Devices (IMDs).
Machine mode support with time discharge.
Illumination (option).
High resolution Loop impendance (mΩ) (option).
EVSE (Electrical Vehicle Supply Equipment) support (option).
Determining location of cables (option).
QR and/or barcode scanner support (option).
LV Electrical Installations In Mobile Homes Video
Metrel MI 3155 EurotestXD Specifications
Function
Specification
Measuring Range
Resolution
Accuracy
CONTINUITY
Test Current 7 mA 2-wire
0.00 Ω ... 19.99 Ω
20.0 Ω ... 1999 Ω
0.1 Ω
1 Ω
+(5 % of r. + 3 digits)
Test Current 200 mA 2-wire, 4-wire
0.00 Ω ... 19.99 Ω
20.0 Ω ... 199.9 Ω
200.0 Ω ... 1999 Ω
0.01 Ω
0.1 Ω
1 Ω
+(3 % of r. + 3 digits)
+(5 % of r.)
+(5 % of r.)
INSULATION RESISTANCE
R iso, R iso all 1
Test Voltage 50/100/250 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 99.9 MΩ
100.0 MΩ ... 199.9 MΩ
0.01 MΩ
0.1 MΩ
0.1 MΩ
+(5 % of r. + 3 digits)
+(10 % of r.)
+(20 % of r.)
R iso, R iso all 1
Test Voltage 500/1000 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 199.9 MΩ
200 MΩ ... 999 MΩ
0.01 MΩ
0.1 MΩ
1 MΩ
+(5 % of r. + 3 digits)
+(5 % of r.)
+(10 % of r.)
R iso, R iso all 1
Test Voltage 2500 V
0.00 MΩ ... 19.99 MΩ
20.0 MΩ ... 199.9 MΩ
200 MΩ ... 999 MΩ
1.00 GΩ ... 19.99 GΩ
0.01 MΩ
0.1 MΩ
1 MΩ
0.01 GΩ
+(5 % of r. + 3 digits)
+(5 % of r.)
+(10 % of r.)
+(10 % of r.)
DAR, PI
0.01 ... 9.99
10.0 ... 100.0
0.01
0.1
+(5 % of r. + 2 digits)
+(5 % of r.)
Varistor test AC, DC 2
0 V . 1000 V (DC)
0 V . 625 V (AC)
1V
+(3 % of r. + 3 digits)
RCD
RCD Uc
0.00 V ... 19.99 V
20.0 V ... 99.9 V
0.1 V
-0 %/+15 %) of r. + 10 digits
(-0 %/+15 %) of r
RCD (t),
0.00 ms ... 40.0 ms
0.0 ms ... max. time
0.1 ms
+1 ms
+3 ms
RCD I Ramp
0.2xI?N ... 1.1xI?N (AC, MI, EV a.c.)
0.2xI?N ... 1.5xI?N (A, I?N ?30 mA)
0.2xI?N ... 2.2xIvN (A, I?N <30 mA)
0.2xI?N ... 2.2xI?N (B, MI, EV d.c.)
0.05xI?N
+0.1xI?N
IMPEDANCE
Zline (L-L, L-N), Ipsc,
Zline 4-wire 3
0.00 Ω ... 9.99 Ω
10.0 Ω ... 99.9 Ω
100 Ω ... 999 Ω
1.00 kΩ ... 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
+(5 % of r. + 5 digits)
>+(10 % of r.)
Zloop (L-PE), Ipfc,
Zloop 4-wire 3
Zs RCD 4
0.00 Ω ... 9.99 Ω
10.0 Ω ... 99.9 Ω
100 Ω ... 999 Ω
1.00 kΩ ... 9.99 kΩ
0.01 Ω
0.1 Ω
1 Ω
10 Ω
+(5 % of r. + 5 digits)
+(10 % of r.)
VOLTAGE
TRMS (0, 14 ... 500 Hz)
0 . 550 V
1 V
+(2 % of r. + 2 digits)
Frequency
0.00 Hz .. 9.99 Hz
10.0 Hz ... 499.9 Hz
0.01 Hz
0.1 Hz
+(0.2 % of r. + 1 digits)
CURRENT
TRMS, AC with A 1018, range=20 A
0.0 mA ... 99.9 mA
100 mA ... 999 mA
1.00 A ... 19.99 A
0.1 mA
1 mA
0.01 A
+(5 % of r. + 5 digits)
+(3 % of r. + 3 digits)
+(3 % of r.)
TRMS, AC with A 1019, range=20 A
0.0 mA ... 99.9 mA
100 mA ... 999 mA
1.00 A ... 19.99 A
0.1 mA
1 mA
0.01 A
Indicative
+(5 % of r.)
+(3 % of r.)
TRMS, AC/DC with A 1391, range=40 A
0.00 A ... 1.99 A
2.00 A ... 19.99 A
20.0 A ... 39.9 A
0.01 A
0.01 A
0.1 A
+(3 % of r. + 3 digits)
+(3 % of r.)
+(3 % of r.)
TRMS, AC/DC with A 1391, range = 300 A
0.00 A ... 19.99 A
20.0 A ... 39.9 A
40.0 A ... 299.9 A
0.01 A
0.1 A
0.1 A
Indicative
Indicative
+(3 % of r. + 5 digits)
EARTH RESISTANCE
3 wire 5
0.00 Ω ... 19.99 Ω
20.0 Ω ... 199.9 Ω
200.0 Ω ... 9999 Ω
0.01 Ω
0.1 Ω
1 Ω
+(5 % of r. + 5 digits)
2 clamp
0.00 Ω ... 19.99 Ω
20.0 Ω ... 30.0 Ω
30.1 Ω ... 39.9 Ω
0.01 Ω
0.1 Ω
0.1 Ω
+(10 % of r. + 10 digits)
+(20 % of r.)
+(30 % of r.)
Specific earth resistance
0.0 Ωm . 99.9 Ωm
100 Ωm ... 999 Ωm
1.00 kΩm ... 9.99 kΩm
10.0 kΩm ... 99.9 kΩm
100 kΩm ... 9999 kΩm
0.1 Ωm
1 Ωm
0.01 kΩm
0.1 kΩm
1 kΩm
+(5 % of r.) for Re 1 Ω . 1999kΩ
+(10 % of r.) for Re 2 kΩ . 19.99kΩ
+(20 % of r.) for Re > 20 kΩ
POWER
Power (P, S, Q)
0.00 W (VA, Var) ... 99.9 kW (kVA, kVar)
Power factor
-1.00 ... 1.00
Voltage THD
0.1 % ... 99.9 %.
HARMONICS
Voltage harmonics
0.1 V ... 500 V.
Voltage THD
0.1 % ... 99.9 %.
Current harmonics and Current THD
0.00 A ... 199.9 A.
FIRST FAULT LEAKAGE CURRENT (ISFL)
ISC 1, ISC 2
0.0 mA ... 19.9 mA
0.1 mA
+(5 % of r. + 3 digits).
IMD TEST
Threshold indicative insulation resistance
5 . 640 kΩ
5 kΩ
Indicative values, up to 128 steps.
ILLUMINANCE
Type B
0.01 lux ... 19.99 lux
20.0 lux ... 199.9 lux
200 lux ... 1999 lux
2.00 klux ... 19.99 klux
0.01 lux
0.1 lux
1 lux
10 lux
+(5 % of r. + 2 digits)
+(5 % of r.)
Type C
0.01 lux ... 19.99 lux
20.0 lux ... 199.9 lux
200 lux ... 1999 lux
2.00 klux ... 19.99 klux
0.01 lux
0.1 lux
1 lux
10 lux
+(10 % of r. + 3 digits)
+(10 % of r.)
DISCHARGING TIME
Discharging time
0.0 s . 10.0 s
0.1 s
+(5 % of r. + 2 digits).
Peak voltage
0 V . 550 V
1 V
+(5 % of r. + 3 digits).
GENERAL
Power supply
7.2 V (4400 mAh Li-Ion battery pack).
Overvoltage category
600 V CAT III; 300 V CAT IV.
Protection class
Double insulation.
COM port
BT, USB, RS232.
Weight
1.78 kg.
Size ( l x h x w )
252 x 111 x 165 mm.
NOTES
1 Measuring current 1 mA ... 3 mA
2 Threshold current 1 mA
3 Itest = 20 A @ 230 V; 16 ... 400 Hz
4 Itest MAX = 0.5 x I?N
5 UOC < 30 VAC, ISC < 30 mA, f = 15 Hz
Metrel A1532 Electric Vehicle Charger Tester Technical Specifications
Input voltage
400 V (3-phase).
Frequency
50 Hz.
Test current
13 A.
Proximity Pilot (PP) simulation
Open circuit
13 A
20 A
32 A
63 A
Control Pilot (CP) simulation
State A (not connected)
State B (connected, not charging)
State C (charging without ventilation)
State D (charging with ventilation)
State E (error - CP short to PE via diode)
Overvoltage category
300 V CAT II.
Protection degree
IP 40.
Pollution degree
2.
Protection classification
Double insulation.
Altitude
3000 m above sea level.
Dimensions (L x W x H)
200 x 100 x 70 mm.
Test lead length
0.5 m.
Weight
0.82 kg.
Working temperature range
0 ?C . 40 ?C @ 95 % RH, non-condensing
Storage temperature range
-10 ?C . +70 ?C.
Maximum storage relative humidity
90 % RH (-10 ?C . +40 ?C)
80 % RH (40 ?C . 60 ?C).
For more information on Metrel MI 3155 EurotestXD Standard talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.