Sign In
The Metrel MI 3108 EurotestPV is a combined photovoltaic tester and electrical installations safety tester. It enables complete testing of electrical installations according to EN 61557 standards and in addition performs all necessary tests required on single-phase photovoltaic (PV) installations.
This includes all of the tests as required by EN 62446, but also includes I - U characteristic, Calculation of STC values as required by EN 61829 and power measurements on Inverter’s DC and AC sides.
The unit is designed for the demanding working conditions (up to 1000 V, with 15 A DC). To greatly improve user safety the MI 3108 EurotestPV comes with the PV Safety Probe which ensures safe disconnection every time.
MEASURING FUNCTIONS
Photovoltaic installations.
Measurements on DC side of PV installation.
Voltage, current, power.
Uoc (Open Circuit Voltage) and Isc (Short Circuit Current).
I - U curve of PV modules and strings.
Irradiance.
Module temperature.
Measurements on AC side of PV installation.
Voltage, current, power.
Efficiency of PV module, inverter, PV system calculation.
Metrel MI3108ST Eurotest PV Tester Specifications
Photovolyaic Installation Measurements
Function
Measuring Range
Basic Accuracy
Voltage
0 V DC ... 999 V DC
0 V AC ... 999 V AC
I-V m.: 0 V DC ... 999 V DC
+(1.5 % of reading + 5 digits)
+(1.5 % of reading + 3 digits)
+(2 % of reading + 2 digits)
Current
Panel m.: 0.0 mA ... 300 A DC
Invert. m.: 0.0 mA ... 300 A AC
I-V m.: 0.00 A ... 15 A DC
+(1.5 % of reading + 5 digits)
+(1.5 % of reading + 3 digits)
+(2 % of reading + 3 digits)
Power
Panel m.: 0 ... 200 kW
I-V m.: 0 ... 15 kW
+(2.5 % of reading + 6 digits)
+(3 % of reading + 5 digits)
Energy
0.000 Wh - 1999 kWh
U/I Curve
1000 V / 15 A / 15 kW
Harmonics
up to 11th
Irradiation
0 ... 2000 W/m2
+(5 % of reading + 5 digits)
Temperature
-10 °C ... + 85 °C
+ 5 digits
Electrical Installation Measurements
Function
Measuring Range
Basic Accuracy
Insulation Resistance (EN61557-2)
U = 50, 100, 250 VDC:
R: up to 199.9 MΩ
U = 500 VDC, 1 kVDC:
R: up to 999 MΩ
+(5 % of reading + 3 digits)
+(5 % of reading + 3 digits)
Continuity, 200 mA
(EN 61557-4)
0.00 Ω ... 1999 Ω
+(3 % of reading + 3 digits)
Continuity, 7 mA
0.0 Ω ... 1999 Ω
+(5 % of reading + 3 digits)
Loop impedance (EN 61557-3)
0.00 Ω ... 9.99 kΩ
+(5 % of reading + 5 digits)
Line impedance (EN 61557-3)
0.00 Ω ... 9.99 kΩ
+(5 % of reading + 5 digits)
Voltage
0 VAC ... 550 VAC
+(2 % of reading + 2 digits)
Frequency
0.00 Hz ... 499.9 Hz
+(0.2 % of reading + 1 digits)
Phase Sequence
1.2.3 or 3.2.1
RCD Testing (EN 61557-6)
I?N: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1 A
Contact Voltage UC
0.0 V ... 99.9 V
(-0 % / +15 %) of reading
Trip Out Time
0 ms ... max. time
+1 ms
Trip-out current
0.2 x I?N ... 2.2 x I?N
+0.1 x I?N
Earth resistance (EN 61557-5)
0.00 Ω ... 9999 Ω
+(5 % of reading + 5 digits)
General
Main Unit
Remote Unit
Display
128 x 64 dots matrix display with backlight
Power Supply
6 x 1.2 V NiMH batteries, type AA
Overvoltage Category
1000 V DC / CAT II
600 V / CAT III; 300 V / CAT IV
Protection Class
Double Insulation
COM Port
RS232 and USB
RS232
Dimensions
230 x 103 x 115 mm
140 x 230 x 80 mm
Weight
1.3 kg
1.0 kg
For more information on Metrel MI3108ST Eurotest Solar PV Tester talk to Cuthbertson Laird Group