Sign In
Individual kits are available for system voltages of 3.3kV, 6.6kV, 11kv, 13.8kV and 33kV (50/60Hz).
The Live Line Tester Kits (LLT) have been specifically designed to perform measurements for both live voltage testing and phasing on overhead lines, in substations and within switchgear compartments.
All components are housed within a heavy duty carry case with secure compartments. Individual kits are available for system voltages of 3.3kV, 6.6kV, 11kv, 13.8kV and 33kV (50/60Hz). Made from high quality fibreglass rods and polycarbonate mouldings the equipment is suitable for both indoor and outdoor use - including wet conditions. The equipment has been designed to operate within the temperature range: - 25 ?C to + 50 ?C.
Designed to comply with the requirements of IEC1243 part 2, the Metrohm LLT 11kV uses long established techniques for high voltage measurement. All readings are displayed on an analogue meter - the housing of which can be rotated through 240 degrees to ensure a perfect viewing position.
A battery operated proving unit allows the equipment to be tested before and after measurements have been made and can also be used to check full scale deflection on the meter. Adaptors are available to allow Bowthorpe Rods to be connected for testing of raised conductors and a Repeater Station can be supplied to replicate meter readings at ground level. Space is reserved in the carry case for such accessories.
SAFETY RULES
Only personnel who are fully trained in the use of Live Line Testers should use this equipment.
Ensure the tester and accessories are clean, free from cracks or deep scores, and are properly secured together.
Make certain that the Tester is properly rated for the voltage of the system under test.
Test the operation of the assembled Tester complete with accessories before and after each test.
Do not allow a live high voltage conductor to come in contact with the detector at point below the limit mark.
The Tester must never be used without a handle or without insulating rods incorporating a handle.
Safe working distances must always be observed.
Always connect the earth lead clip to a secure earthing point before performing a test.
FEATURES
Self powered operation.
Designed for indoor & outdoor use.
Positive phasing test.
High voltage measurement.
High quality fibreglass rod.
Proving & repeater units.
Designed to comply with the requirements of IEC1243 part 2.
High immunity to interference fields.
Metrohm LLT11kV Specifications
11 kV Tester
Resistor Chain
75 MΩ.
Measuring Range
15 kV.
Accuracy
+5% FSD.
Length
1025 mm.
Weight
1.4 kg.
Phasing Rod
Length
1025 mm.
Weight
1.4 kg.
Extension Rod
Length
907 mm.
Weight
0.65 kg.
Proving Unit
Voltage output
3 to 5 kV.
Dimensions
185 x 145 x 120 mm.
Repeater Station
Used in conjunction with the tester/Ph rod
Dimensions
185 x 145 x 120 mm.
Bent End Adaptor
Length
675 mm.
Weight
0.27 kg.
Overhead Line Adaptors
Height
100 mm.
Weight
0.08 kg.
Bowthorpe Rod Adaptor
Length
360 mm.
Weight
0.62 kg.
Connection Cable
12 m.
LLT11kV warranty
One-year.
For more information on Metrohm 11kV Live Line Tester - LLT11kV talk to Cuthbertson Laird Group
Enquire Now