Sign In
The Seaward PR11 phasing sticks provide a means of phase comparison at the point of paralleling two circuits, without the interposition of voltage transformers or secondary wiring circuits. A neon type instrument, it is designed for use on earthed neutral circuits up to 11kV.
FEATURES
For use on 1kV to 11.5kV systems.
PVC hand guards on handles of elements.
Neon indicator enclosed in shock resistant sleeve.
Direct areas possible to all types of switch gear.
Complies with UK Electricity Council Engineering recommendation G9.
Bent adaptors available for use with switch gear.
Seaward PR11 Specification
Maximum System voltage
11 kV.
Maximum Voltage to earth
6.6 kV.
Threshold voltage
300 V.
Measuring Range
N/A
Resolution
N/A
Sensitivity
AC /DC.
Circuit current (IEC 61234-2)
0.9 mA nominal @11.5 kV.
Dielectric leakage current (IEC 61234-2)
25 uA nominal @ 13.8 kV.
Length (mm)
330.
Diameter (mm)
25.
Handle length (mm)
105.
Hand guard height (mm)
23.5.
Contact Electrode Type
Domed.
For more information on Seaward PR11 11kV Phasing Rods talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.