The T&R 100A/E Mk3** unit is portable, compact and simple to use. The mains supply for the unit is either 240V+10% or 115V +10% -6% at either 50 or 60Hz. Full load can be obtained at the supply voltage extremes.
The current and voltage outputs are independently controlled and metered. The output current and voltage are displayed on large, clear panel instruments. An additional four range CT is provided, extending the ammeter range down to 0-100mA.
The current output on the 100A/E Mk3 has eight ranges, allowing the selection of output voltages up to 150V and output currents up to 200A. The current outputs may also be used as voltage outputs.
All of the outputs are fully isolated by means of double wound transformers. The type 100A/E MK3 S.C.I.T.S. is housed in a robust steel case, complete with fold away carry handles. The unit is fitted with a detachable cover in which is housed the spare fuse carrier and rating/scale factor plate.
** If using a 100ADM-F with this unit then you will need to order A006-0010 output lead set.
FEATURES:
Wide range of output currents.
AC and DC voltage outputs.
All outputs continuously variable.
Output current metering from 40mA - 200A.
Automatic switch-off in all modes of operation.
Multi-function timing system.
Suitable for testing thermal devices.
Compact and highly portable.
Voltage and current outputs available simultaneously.
T&R 100A/E Specifications
Current Output
Range
Continuous
5 Minutes
1 Minute
VAC
200 A
50 A
100 A
200 A
0-5 V
50 A
25 A
50 A
-
0-10 V
25 A
12.5 A
25 A
-
0-20 V
10 A
5.0 A
10 A
-
0-50 V
5.0 A
2.5 A
5.0 A
-
0-50 V
2.5 A
1.25 A
2.5 A
-
0-50 V
1.0 A
0.5 A
1.0 A
-
0-150 V
Voltage Output
Voltage
Output Current
Range
Continuous
5 Minutes
0 to 250 V AC
0.5 A
1.0 A
0 to 500 V AC
0.25 A
0.5 A
0 to 250 V DC
0.5 A
1.0 A
Metering
Range
1A Scale
5A Scale
Accuracy
0.1 A
x 0.1
x 0.02
Class 1.5
0.25 A
x 0.25
x 0.05
Class 1.5
0.5 A
x 0.5
x 0.1
Class 1.5
1.0 A
x 1
x 0.2
Class 1.5
2.5 A
x 2.5
x 0.5
Class 1.5
5.0 A
x 5
x 1
Class 1.5
10 A
x 10
x 2
Class 1.5
25 A
x 25
x 5
Class 1.5
50 A
x 50
x 10
Class 1.5
100 A
x 100
x 20
Class 1.5
200 A
x 200
x 40
Class 1.5
Timing System
Range
0 to 999.999s.
Resolution
1ms.
Accuracy
+0.1% rdg + 2d (all modes except current op.)
Accuracy
+0.1% rdg +3d (current operated mode).
Functions
Mode
Timer Start
Timer Stop
Internal Start
Press On
Contact 1
Single Contact
Contact 1
Contact 1
Dual Contact
Contact 1
Contact 2
Current Operated
Current > 20% of range
Current <20% of range
Protection and Safety
Input Supply
T5 A 240 V supply
T10 A 115 V supply.
Output Supplies
T3.15 A.
Contact
F0.25 A.
Auxiliary CT Circuit
T315 mA and T1.25 A.
Supply Requirements
115V + 10% - 6%: 50/60 Hz 1ph 1450 VA max
240V + 10%: 50/60 Hz 1ph 1450 VA max.
Temperature Range
Storage
-20 to 60°C.
Operating
0 to 45°C.
Other Specs
Dimensions
490 x 300 x 300 mm.
Weight
33 kg.