Sign In
The T&R 750ADM mk3 is a flexible current injection system capable of supplying currents of up to 750A ac into a variety of loads. The unit is designed for testing devices used for power system protection, but can be used wherever a high current AC source is required. The 750ADMH mk3 has a maximum no load output voltage of 5V. The unit is ideally suited to all low power primary injection tasks requiring up to 750A for short periods.
The unit has two outputs, allowing injection of currents as low as a few hundred milliamps and up to 750A. Voltages up to 16V are available on the 40A output, allowing higher impedance trips to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output.
FEATURES
Primary injection up to 750A.
4V output*
16V 40A output for secondary injection.
True RMS memory ammeter with singlecycle capture.
Multi-function timing system.
Large back-lit liquid crystal display.
Thermal and over-current protection.
Automatic switch-off at end of test.
Compact and portable.
Automatic mains voltage selection*.
* See specifications.
T&R 750ADM-H mk3 Specifications
Main Output
115 V
230 V
750 A Output
Open Circuit Voltage
3.5 V
5.0 V
Voltage at 500A
2.8 V
4 V
Continuous Current
125 A
125 A
5 Min On
250 A
250 A
1 Min On
440 A
500 A
Max Current
500 A
750 A
Max Current On Time
10 s
20 s
40 A Output
Open Circuit Voltage
10 V
16 V
Full Load Voltage
7.5 V
10 V
Continuous Current
10 A
10 A
1 Min On
40 A
40 A
Metering
Range
Resolution
Trip Current
Accuracy
20.00 A
0.01 A
21 A
+0.5%rdg+5d.
50.00 A
0.01 A
53 A
+0.5%rdg+5d.
200.0 A
0.1 A
210 A
+0.5%rdg+5d.
750 A
1 A
788 A
+0.5%rdg+2d.
Timing System
Range
0-999.999s/9999.99s/99999.9s auto-ranging.
Resolution
1ms/10ms/100ms.
Accuracy
+0.01%rdg+2d (all modes except current operated)
+0.01%rdg+4d (current operated mode).
General Specifications
Supply Requirements (self selecting)
115V+10% 50/60Hz 1ph, 1900 VA max
230V+10%, 50/60 Hz 1ph, 3900 VA max.
Storage Temperature
-20°C to 60°C.
Operating Temperature
0°C to 45°C.
Dimensions
560 x 456 x 265 mm.
Weight
27.4 kg.
T&R 750ADM-H mk3 warranty
One-year.
For more information on T&R 750ADM-H mk3 PCITS talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.