Sign In
The Z-OVR is a line/cable impedance measurement system for high voltage ac systems.
The impedance of the line is measured by injecting a current and measuring the magnitude and phase angle of the voltage developed across the line. The resistance and reactance of the line are calculated from these results and displayed. The system uses a 4-wire measurement with a Kelvin connection to the line under test to eliminate measurement errors due to voltage drops in the leads.
The system consists of a separate control unit containing all metering and control functions and an output unit that provides the high current output and isolation of measured voltages. All connections to the line are made via the output unit.
The unit has data logging facilities using a standard USB memory key. Date, time, current, voltage, phase angle, and frequency are stored to a CSV file on the memory key along with a comment entered using the supplied USB keyboard.
The Z-OVR system must only be used on ‘dead’ systems (i.e. no externally supplied voltages are present on the test object) with safety earths applied.
FEATURES
Measure impedance of overhead lines and underground cables.
Direct readout of cable Z & X.
Phase angle display.
Voltage up to 300V.
Current up to 80A.
Data storage to CSV file on USB memory key.
Digital true RMS memory ammeter & voltmeter.
Solid state switching.
Rugged, compact design.
T&R Specifications
Current/Voltage Ranges
Range
Full Scale
Resolution
Accuracy
2A
2.000A
0.001A
+1%rgd+5d
10A
10.00A
0.01A
+1%rgd+5d
20A
20.00A
0.01A
+1%rgd+5d
100A
100.0A
0.1A
+1%rgd+5d
30V
30.00V
0.01V
+1%rgd+5d
300V
300.0V
0.1V
+1%rgd+5d
Phase
0 - +180.0°
0.1°
+1°
Output Rating
Current Rating
Ouput
Continuous
5 Min On
Maximum
75V - 80A
40A
80A
80A
150V - 40A
20A
40A
40A
300V - 20A
10A
20A
20A
Protection & Safety
CE Marked
Yes.
Meets
BS EN61010.
Protection
Electronic trips on outputs.
Circuit Breakers on mains input and outputs.
Duty cycle trip on loading unit output.
Thermal protection.
Storage
Yes, on USB memory key.
Real-time clock
Yes.
Operating temperature
0°C to 45°C.
Storage temperature
-20°C to 60°C.
Supply requirements
230V+10%
45-65Hz 1ph
7kVA max.
Dimensions
Z-OVR: 450(w) x 275(h) x 305mm(d)
NLU75/80: 450(w) x 275(h) x 330mm(d).
Weight
Z-OVR: 26 kg
NLU75/80: 50 kg.
T&R Z-OVR Warranty
2 years.
For more information on T&R Z-OVR Cable Impedance Test Set talk to Cuthbertson Laird Group
Enquire Now
List your company on FindTheNeedle.