Sign In
DescriptionHighly accurate manganin resistance d.c shunts. When a current is passed through the shunt a proportional millivolt output is produced.Our standard range of BS89/IEC51 class 1 or class 0.5 shunts can be current rated from 5A to 10000A with 50mV to 300mV output.ApplicationShunts are used for measuring current in d.c. applications by connecting them to moving coil panel meters, digital meters or other measuring devices. Shunts can also be used in control devices such as power supplies and battery chargers for overload protection.. Techinical SpecificationOperating Temperature:-20C TO +40CPermissible Overload:Continuous1.2 x rated current5 seconds5 x rated current up to 2kA10 seconds2 x rated current for 2kA-5kAShunt Leads:Millivolt leads can be supplied uponrequest (standard length = 760mm)Order example:A brass ended shunt with 1000A ratedcurrent and 100mV output, class 1 is:SHB1000A100-CLASS1DimensionsABCDEFCurrent (A)Type50mV60mV75mV100mV150mV200mV250mV300mV5-351959595114114172172267221011?740-2001959595114114172172267321213?10225-4401959595114121172172267322025?10450-75029595951141211721722676716254110800-1600295959511412117217226767252541101700-34003959595114121172??111388157103500-50003959595114121???1403811490125500-70004838396?????2303811490127500-100005838396?????320381149012
For more information on Standard Brass Ended Shunts For Business talk to Howard Butler Ltd