Sign In
DescriptionDIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail casesApplicationUsed to conver various inputs into standard DC signals for driving panel meters and for use in control devices.?Selection GuideM100-TAPResistance measurementTypical ApplicationsThe M100-TAP measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decreases respectively, The M100-TAP measure the value of this resistance and provides an output proportional to the value of the number of taps selected. The M100-TAP can also be used to measure variable resistance 2 or 3 wire systems.Technical SpecificationsINPUTRated Rangemin 100 ohms ..max 20kOhmsSensor Currentmin 50uA..max 10mASensor Voltage< 1 VoltWorking Range0-125% RnOUTPUTRated value mA0-1/5/10/20 & 4-20mARated value volts0-5/10 & 1-5VADJUSTMENTZero±2%Span±10%AUXILIARYA.C. Voltage115/230/400V(±25% / 45-65Hz / 2VA)D.C. Voltage24/48/110V(±20% / galvanically isolated/ <3W)WEIGHT&CASE SIZEApprox 0.4kg. 55mm caseNOTENo isolation is provided between input and outputOrdering InformationProduct CodeNo TapsOutputAuxFreqOptionsM100-TAP105mA230V50HzOptions1Non standard Inputs/Outputs as far as technically viable2A.C. Auxiliary in range 57.7 to 450 volts3Calibration at temperature other than 23CA.C. Current Connection Diagrams
For more information on Tap Position Transducers talk to Howard Butler Ltd
Enquire Now