The D0400 is for connection of up to 8 detectors in parallel without indication.
To be installed considering the length of the detector cables (5 metres), Junction boxes with indication are installed so that the LEDs are fully visible. Max. 2 Junction Boxes per Arc Detection Relay.
This product is complementary to the following products:
- A0200 Detector
- A0300 Detector
- D0100 Arc Detecting Relay
- D0900 Arc Detecting Relay
The unit D0500 is designed to connect up to 8 detectors in parallel and has a separate indication of which detector(s) caused tripping by means of a red LED for each detector. The red LED is lit when the light intensity exceeds 6.000 lux. on the detector, but it turns off again if the intensity goes below 6.000 lux. At 12.000 lux. the Arc Detecting Relay is triggered, the active LEDs are latched and a yellow LED (TRIP) is turned on. All LEDs remain turned on until reset by a common RESET button. Max. 2 boxes per arc detecting relay is allowed.
This product is complementary to the following products:
- A0200 Detector
- A0300 Detector
- D0100 Arc Detecting Relay
For more information on D0400 And D0500 Junction Box talk to KCG Electronics Ltd