In a factory setting, it may be desirable to limit the access of the cMT X Series web browser. We can do this by unchecking “Show navigation bar” and using the Control registers instead. Control Word Codes: 1 – Go 2 – Reload 3 – Stop 4 – Back 5 – Forward 6 – Clear Cache 7 – Clear Cookies Example using “Set word” for a “Back” button For the favourites buttons, we’re using a “Combo Button” with 2 Actions Action 1 – Write constant string with our URL Action 2 – set the control word to “1” for “Go” Repeat for shortcuts required. As usual, we have a demo project for you to try out here.
For more information on TechTip: Weintek cMT X Series PLC Web Browser Object talk to Lamonde Automation Ltd