Sign In
Compressor Replacement on Samsung Condenser
12-11-2020
Job Description: Compressor Replacement on Samsung Condenser
Area: Savoy Place, London
Issue Identified: Following a call out, the engineer advised that the compressors had failed and required replacing. The main inverter compressor had burnt out and the main inverter board also required replacing at the same time.
Works carried out:
Isolated the unit electrically and mechanically.
Recovered refrigerant into a dedicated recovery cylinder for safe disposal.
Removed and replaced compressors, including hot works.
Removed and replaced the inverter compressor.
Pressure tested the system with Oxygen Free Nitrogen (OFN) and confirmed leak tight.
Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
Re-charged with virgin refrigerant.
Test ran and re-commissioned.
Completed waste transfer note and handed to on-site representative.
Completed F Gas records and cleared site.
For more information on Compressor Replacement on Samsung Condenser talk to Aces Group Ltd
Enquire Now
List your company on FindTheNeedle.